Add the following table to the bottom of page 2-4 – Fluid Components International FLT Series Rack Mount User Manual

Page 61

Advertising
background image

ERRATA 17EN000019 Rev. A

Fluid Components Intl

(Apply to Doc. No. 06EN003250 Rev. N/C)

2

FLT

Series FlexSwitch

Rack Mount

INSTALLATION CONFORMITY CRITERIA

Grounding

All enclosures must be grounded to earth ground through a path of less than 1 ohm.

Interconnecting Cables

All interconnecting cables between the FlexSwitch local enclosure, remote enclosure, power source and monitoring
device shall be enclosed in metal conduit.

Standard ESD Precautions

Use standard ESD precautions when opening an instrument enclosure or handling the FlexSwitch. FCI recommends
the use of the following precautions: Use a wrist band or heel strap with a 1 megohm resistor connected to ground.
If the instrument is in a shop setting there should be static conductive mats on the work table and floor with a 1
megohm resistor connected to ground. Connect the instrument to ground. Apply antistatic agents to hand tools to be
used on the instrument. Keep high static producing items away from the instrument such as non-ESD approved
plastic, tape and packing foam.

The above precautions are minimum requirements to be used. The complete use of ESD precautions can be found in
the U.S. Department Of Defense Handbook 263.

Location of CE mark documentation (European Location)

The technical documentation file part A resides at Fluid Components Intl, European Service Center, Beatrix De
Rijkweg 8, 5657 Eg Einhoven, Netherlands, PH: 31-40-2-571-972 FAX: 31-40-2-517-809.

Location of CE mark documentation (Manufacturer Location)

The technical documentation file part B resides at the Configuration Management department of Fluid Components
Intl, 1755 La Costa Meadows Dr. San Marcos, Ca. 92069 USA.

Add the Following Table to the

Bottom of Page 2-4:

Table 2-2. Maximum AWG Number For Wiring the Instrument

Connection

Maximum Distance for AWG

10 ft.

(3m)

50 ft.

(15m)

100 ft.

(31m)

250 ft.

(76m)

500 ft.

152m)

1000 ft.

(305m)

AC Power

22

22

22

20

18

16

Relay (2A)

28

22

20

16

12

10

Flow Element Wires*

22

20

20

18

18

18

*Requires a shielded cable with the shield wire connected to the control socket only.