OPERATION

FLT

®

Series FlexSwitch

TM

20

Fluid Components International LLC

Alarm Set Point Adjustments

Numerical Adjustment Versus Adjustment by Observation

An alarm set point is established using either numerical adjustment or adjustment by observation. The adjustment by observation requires
the customer to establish normal process operation and adjust the alarm set point relative to this condition. The numerical approach requires
measuring normal and alarm process conditions with a voltmeter and setting up the instrument in the calibrate mode based on these values.
The adjustment by observation requires less time to establish the alarm set point. The numerical adjustment requires control of the process
as well as additional time to establish the alarm set point. Use the adjustment procedure that is the most appropriate for the application
requirement.

Figure 3-1 5298 Control Circuit Jumper Locations

Jumper

Power Select - Factory Installed

100-130 VAC

200-260VAC

18-26VAC

21-30VDC

J1

IN

OUT

OUT

OUT

J2

OUT

IN

OUT

OUT

J3

IN

OUT

OUT

OUT

J4

OUT

OUT

IN

OUT

J5

IN

IN

OUT

OUT

J6

OUT

IN

IN

IN

J7

OUT

OUT

OUT

IN

J8

OUT

OUT

OUT

IN

J9

OUT

OUT

IN

OUT

Table 3-2 Input Power