FLT

®

Series FlexSwitch

TM

OPERATION

Fluid Components International LLC

21

Jumper

J32

J12

J13

J14

J33

FLT93-F ELEMENT WATTAGE

(560 OHM HTR)

0.57

WATTS

0.52

WATTS

0.49

WATTS

0.20

WATTS

OFF

FLT93-S ELEMENT WATTAGE

(110 OHM HTR)

3

WATTS

1.75

WATTS

0.75

WATTS

0.27

WATTS

OFF

Table 3-3A Selectable Heater Wattage Control

J13 is standard for FLT93-S and J14 is standard for FLT93-F

Jumper

J13

J14

J33

FLT93-F ELEMENT WATTAGE

(560 OHM HTR)

N.A.

0.20

WATTS

OFF

FLT93-S ELEMENT WATTAGE

(110 OHM HTR)

0.75

WATTS

N.A.

OFF

Table 3-3B Fixed Heater Wattage Control

FLOW/LEVEL

TEMP

ALARM NO. 1

J20

J21

ALARM NO. 2

J18

J19

Table 3-4 Application

Jumper

ALARM NO. 1

J27

RELAY DE-ENERGIZED WITH LOW FLOW, LOW LEVEL
(DRY) OR HIGH TEMPERATURE.

J26

RELAY DE-ENERGIZED WITH HIGH FLOW, HIGH LEVEL
(WET) OR LOW TEMPERATURE.

Jumper

ALARM NO. 2

J25

RELAY DE-ENERGIZED WITH LOW FLOW, LOW LEVEL
(DRY) OR HIGH TEMPERATURE.

J24

RELAY DE-ENERGIZED WITH HIGH FLOW, HIGH LEVEL
(WET) OR LOW TEMPERATURE.

Table 3-5 Relay Energization

J23

DUAL SPDT (ONE RELAY PER ALARM)

J22

SINGLE DPDT (DISABLES ALARM NO. 2)

Table 3-6 Relay Contact Confi guration