Fail safe alarm setting, Low flow alarm setting, High flow alarm settings – Fluid Components International FLT93 Nuclear User Manual

Page 37

Advertising
background image

FLT

®

Series FlexSwitch

TM

OPERATION

Fluid Components International LLC

37

Fail Safe Alarm Setting

These procedures set the second relay to detect component failure (fail-safe).

Low Flow Alarm Settings

For the low fl ow fail safe setup the following jumpers are to be installed: J18, J20, J23, J24, J27.

The following information is assumed:

Relay is de-energized in the ALARM condition.

Alarm 1 set point is adjusted for desired low fl ow alarm velocity or signal.

Alarm 2 set point is adjusted slightly below minimum signal output (over range fl ow).

High Flow Alarm Settings

For the high fl ow fail safe setup the following jumpers are to be installed: J18, J20, J23, J25, J26.

The following information is assumed:

Relay is de-energized in the ALARM condition.

Alarm 1 set point is adjusted for desired high fl ow alarm velocity or signal.

Alarm 2 set point is adjusted above maximum signal output (under range fl ow not to exceed 7.0 volts).

Figure 3-5. Low Flow Fail Safe Alarm

0.5

0

20

10

30

50

40

60

1.0

0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

WHEN ALARM 1 DETECTS HIGH FLOW
THERE IS A POSSIBLE SHORTED
ACTIVE RTD OR OPEN REFERENCE
RTD

ALARM 2 DETECTS A POSSIBLE
OPEN ACTIVE RTD OR SHORTED
REFERENCE RTD

SIGNAL

OUTPUT

AIR FLOW RATE

SET POINT 2

SET POINT 1

DE-ENERGIZED

DE-ENERGIZED

ENERGIZED

ENERGIZED

C00535-1-2

A POWER FAILURE IS DETECTED IF
BOTH RELAYS ARE DE-ENERGIZED

Figure 3-6. High Flow Fail Safe Alarm

0.5

0

20

10

30

50

40

60

1.0

0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

WHEN ALARM 1 DETECTS LOW FLOW
THERE IS A POSSIBLE OPEN ACTIVE
RTD OR SHORTED REFERENCE RTD

WHEN ALARM 2 DETECTS OVER
RANGE FLOW, THERE IS A POSSIBLE
HEATER FAILURE, SHORTED ACTIVE
RTD OR OPEN REFERENCE RTD

SIGNAL

OUTPUT

AIR FLOW RATE

SET POINT 1

SET POINT 2

DE-ENERGIZED

DE-ENERGIZED

ENERGIZED

ENERGIZED

C00534-1-2

A POWER FAILURE IS DETECTED IF
BOTH RELAYS ARE DE-ENERGIZED