TM

OPERATION

Fluid Components International LLC

25

7. Raise the process fl uid level so the sensing element is wet.

8. Allow the output signal to stabilize and record the wet condition value.

Wet Condition Signal = ________ volts DC

Note:

The output signal at P1 is relative to the type of process media detected. See Figure 3-4.

9. Lower the process fl uid level so the sensing element is dry.

10. Allow the output signal to stabilize and record the dry condition value. (The dry signal should be greater than the wet signal.)

Dry Condition Signal = ________ volts DC

11. Determine the set point by calculating the average of the wet and dry output signals. (i.e., If the wet signal is 0.200 volts and the dry

signal is 4.000 volts, then the calculated set point would be 2.100 volts.)

12. Record this value.

Calculated Set Point = ________ volts DC

Note:

The calculated set point must be at least 0.015 volts greater than the wet signal and 0.020 volts less than the dry signal to
ensure that the alarm will reset.

13. Slide the mode switch to the CALIBRATE position.

14. Adjust the calibrate potentiometer (R24) until the voltmeter equals the calculated set point.

15. For the appropriate alarm, determine whether the status LED is on or off (red for No. 1 or green for No. 2).

16. Follow either the Detecting Dry Condition or the Detecting Wet Condition for each level application alarm.

Detecting Dry Condition (low level alarm)

If the status LED is off, turn the set point adjustment potentiometer (R26 for alarm No. 1 or R25 for alarm No. 2) slowly clockwise just
until the LED turns on.

OR

If the status LED is on, turn the set point adjustment potentiometer (R26 for alarm No. 1 or R25 for alarm No. 2) counterclockwise until
the LED turns off and then slowly clockwise just until the LED turns on.

Figure 3-4 Level Application Signal Output

SET POINT

TIME

OUTPUT VOL

T

A

G

E

AIR OR GAS

OIL

WATER

LED ON

ABOVE SETPOINT

LED OFF

BELOW SETPOINT

R25 AND R26

Adjust

Clockwise,

Turns

LED ON

Adjust

Counter-

clockwise,

Turns

LED OFF

FIELD ADJUSTABLE

SET POINT

0

Potentiometer

(POT)

DIESEL

AIR

TO

WA

TER

WA

TE

R T

O A

IR

C00070-1-2