OPERATION

FLT

®

Series FlexSwitch

TM

38

Fluid Components International LLC

Low Level Alarm Settings (Sensing Element Normally Wet)

For the low level fail safe setup the following jumpers are to be installed: J18, J20, J23, J24, J27.

The following information is assumed:

Relay is de-energized in the ALARM condition.

Alarm 1 set point is adjusted for the mean value between the air and liquid signals.

Alarm 2 set point is adjusted to approximately half of the liquid signal. (A lower setting might be needed if the liquid is moving.)

High Level Alarm Settings (Sensing Element Normally Dry)

For the high level fail safe setup the following jumpers are to be installed: J18, J20, J23, J25, J26.

The following information is assumed:

Relay is de-energized in the ALARM condition.

Alarm 1 set point is adjusted for the mean value between the air and liquid signals.

Alarm 2 set point is adjusted above maximum signal output for air (not to exceed 7.0 volts).

0.5

1.0

0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

WHEN ALARM 1 DETECTS LOW
LEVEL, THERE IS A POSSIBLE
OPEN ACTIVE RTD OR SHORTED
REFERENCE RTD

WHEN ALARM 2 DETECTS UNEXPECTED
FLOW THAT FORCES THE SIGNAL
BELOW THE ALARM SET POINT, THERE
IS A POSSIBLE HEATER FAILURE,
SHORTED ACTIVE RTD OR OPEN
REFERENCE RTD

SIGNAL

OUTPUT

MEDIA

ALARM 1

SET POINT

DE-ENERGIZED

ENERGIZED

ENERGIZED

C00534-2-2

ALARM 2

SET POINT

AIR

LIQUID

A POWER FAILURE IS DETECTED IF
BOTH RELAYS ARE DE-ENERGIZED

DE-ENERGIZED

Figure 3-7. Low Level Fail Safe Alarm

0.5

1.0

0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

ALARM 2 DETECTS A POSSIBLE OPEN
ACTIVE RTD OR SHORTED REFERENCE
RTD

WHEN ALARM 1 DETECTS HIGH LEVEL,
THERE IS A POSSIBLE HEATER FAILURE,
SHORTED ACTIVE RTD OR OPEN
REFERENCE RTD

SIGNAL

OUTPUT

MEDIA

ALARM 2

SET POINT

ALARM 1

SET POINT

DE-ENERGIZED

DE-ENERGIZED

ENERGIZED

ENERGIZED

C00535-2-2

AIR

LIQUID

A POWER FAILURE IS DETECTED IF
BOTH RELAYS ARE DE-ENERGIZED

Figure 3-8. High Flow Fail Safe Alarm