5080 counter/ command set frequency module, Aasi – Advantech 5000 Series User Manual

Page 193

Advertising
background image

5080 Counter/

Command Set Frequency Module

#aaSi

However, if the response is in frequency mode, you'll
see one similar to the example below:

>0000098700000006490000000762000000011600(cr)

As all 4 values are concatenated into one numerical
string such as above, we can still easily discern the
values of 4 channels specifically as:

0000098700,0000064900,0000076200,0000011600

What you see here is actually the input

values of all channels returned from slot 2 of the ADAM-
5000 system at address 16h and in decimal format.
However, it is not the actual frequency.

Each actual frequency can be obtained

by dividing the response value by 100. Therefore,
taking an example of the value above, the actual
frequency should be:

actual frequency = 98700/100 = 987

If the response is:

>0000F1000002000000031000000DD400(cr)

The command requests the module in slot 2 of the
ADAM-5000 system at address 16h to return the input
values of all channels.

The module response that input values if all channels
are hexadecimal:

0000F100,00020000,00031000,000DD400

The actual frequency can be obtained by transferring
hexadecimal format to decimal format .Then divide the
response value by 100. Therefore, taking an example
of the value above, the actual frequency should be:

F100 (hexadecimal)=24100 (decimal)

actual frequency = 24100/100 = 241

6-128

ADAM-5000