Chapter 6 – Advantech 5000 Series User Manual

Page 218

Advertising
background image

Chapter 6

$aaSiCAhCSkCh

Name

Set Alarm Connection

Description Connect the High/Low alarm of the specified input

channel to the specified digital output in the addressed
ADAM-5000 system

Syntax $aaSiCjAhCSkCn(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.

SiCj identifies the desired slot i and the desired channel
j . AhC is the command for setting Alarm Connection
command.

h indicates alarm type and can have the value H = High
alarm, L = Low alarm

SkCn identifies the desired slot k and the desired
digital output point n (n : 0 to F). To disconnect the
digital output, k and n should be set as ‘*’.

(cr) represents terminating character, carriage return (0Dh)

Response !aa(cr) if the command was valid

There is no response if the system detects a syntax error
or communication error or if the specified address does
not exist.

! delimiter character indicating a valid command was
received.

aa represents the 2-character hexadecimal address of the
corresponding ADAM-5000 system.

(cr) represents terminating character, carriage return (0Dh)








ADAM-5000

6-153