Chapter 6

$aaSiCjRhC

Name

Read Alarm Connection

Description Return the High/Low alarm limit output connection of a

specified input channel in the addressed ADAM-5000
system

Syntax $aaSiCjRhC(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.

SiCj identifies the desired slot i and the desired channel j.

RhC is the command for reading Alarm Connection.

h indicates alarm type and can have the value H = High
alarm, L = Low alarm

(cr) represents terminating character, carriage return (0Dh)

Response !aaSkCn(cr) if the command was valid

There is no response if the system detects a syntax error
or communication error or if the specified address does
not exist.

! delimiter character indicating a valid command was
received.

aa represents the 2-character hexadecimal address of the
corresponding ADAM-5000 system.

SkCn identifies the desired slot k and the desired
digital output point n (n : 0 to F) to which the input alarm
is connected. If the values of k and n are ‘*’, the
analog input has no connection with a digital output
point.

(cr) represents terminating character, carriage return (0Dh)