Chapter 6 – Advantech 5000 Series User Manual

Page 202

Advertising
background image

Chapter 6

$aaSiCj5

Name

Read counter Start/Stop

Description Requests the addressed counter/frequency module to

indicate whether counters are active.

Syntax $aaSiCj5(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system.

SiCj identifies the I/O slot i and the channel j of the
module you want to set.

5 is the command for reading counter Start/Stop.

(cr) is the terminating character, carriage return (0Dh)

Response !aas(cr)

if the command is valid.

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax error or
communication error or if the specified address does not
exists.

! delimiter character indicating a valid command was
received.

? delimiter character indicating the command was
invalid.

aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.

s represents start/stop command.
s=0 indicate stop counter.
s=1 indicate start counter.

(cr) is the terminating character, carriage return (0Dh)







ADAM-5000

6-137