A) commission the lonworks routers, Commission the control neuron processors – CTI Products NCB/FL with Fiber Interface User Manual

Page 19

Advertising
background image

CTI Products, Inc.

NCB-EL/FL User Guide

2. Installation

16

S

TEP

7. C

OMMISSION THE

R

OUTERS AND

C

ONTROL

N

EURON

P

ROCESSORS

Once the NCB unit IP Address Parameters are set (steps 4 and 5) and the NCB units are physically installed in
the IP and L

ON

W

ORKS

networks (step 6), the router and control neuron processor portions of each NCB unit

must be commissioned with the L

ON

W

ORKS

network management tool. Once all units have been

commissioned, the Channel Delay parameter of the custom Ethernet channel should be adjusted to match actual
conditions.

If using LonMaker for Windows, proceed as follows:
A) Commission the L

ON

W

ORKS

routers:

• Commission the router of the NCB whose NETWORK port is attached to the PC used for network

management by right-clicking on the router shape, then clicking on the “Commission” function.

• click NEXT, then FINISH to commission the first router.
• Repeat the above to commission the router portion of all other NCB units on the channel.

B) Commission the Control Neuron Processors:

• Commission a Control Neuron Processor (in any order) by right-clicking on the device shape, then

clicking on the “Commission” function.

• click NEXT, then NEXT again, then select Online and click FINISH to commission the device.
• Repeat the above to commission the Control Neuron Processors of all other NCB units on the channel.

C) Use the “Ping” function to determine message transit time over Ethernet IP channel:

• Launch EtherPlug. (See Step 3)
• Right-click on the first Member Name in the Channel Member List, then choose “Ping” from the

selection. The “Ping” request window will be displayed as shown below (left).

• Click Ping to cause the ping to be initiated.
• From the “Ping Results” window (shown below right), record the “Max:” time (maximum round-trip

message time) for this member.

• Ping the remainder of NCB members (except for the NCB unit connected to the PC on which the

network management tool is being run), recording the “Max:” time for each

D) Update “CUSTOM Channel Delay” in LonMaker for Windows:

• Right-click on the CUSTOM (Ethernet) channel created in Step 2A above. In the drop-down list, click

“Properties”. The “Channel Properties” window will be displayed.

• In the “Delay” section of the “Channel Properties” window, choose “Specify”, and enter a value that

is twice that of the largest “Max:” time found in Step 7C. Then Click OK .

The installation of the NCB units is now complete.