Appendix D. Troubleshooting

31

Table D6

Miscellaneous:

REASON

CORRECTIVE ACTION

Cannot communicate with

Control Neuron Processor
of local NCB when using
NODEUTIL.

1. In Bridge or Configured modes, router

neurons and network interface are not in
the same domain.

2. In Repeater mode, the network interface

may be defective.

1.

Verify that NODEUTIL can
communicate with another L

ON

W

ORKS

node.

2a. Place the local router in Repeater mode

and verify that communications is
possible, or

b. Use NODEUTIL to change the

network interface Domain to match the
router neurons’ domains.

Cannot communicate with the

Control Neuron Processor
of local NCB.

1. In Bridge or Configured modes, the

Control Neuron, the router neurons, and
the network interface are not all in the
same domain.

2. In Repeater mode, the Control Neuron

and network interface are not in the same
domain.

1.

Place the local router neurons in
Repeater mode.

2.

Change the network interface Domain
to match the Control Neuron domain.

Cannot commission the

Control Neuron
Processor when using
LonMaker for
Windows.

Incorrect external interface definition

(.xfb or .xif file) was specified when
commissioning node.

Use NCBEL20 for Version 2 NCB-

Etherlon or NCB-Fiberlon.