NCB-EL/FL User Guide

2. Installation

5

F

RONT

P

ANEL

1

2

3

4

5

9

8

7

6

ERR

ACT

PWR

RESET

WINK

ETH RX

ETH TX

CSVC

RSVC

NETWORK

OUT

IN

ASYNC

NETWORK

NCB

NETWORK COMBINER

Figure 3 NCB-Etherlon and NCB-Fiberlon Front Panel

Front Panel Indicators – Additional Information

ETH RX LED (Yellow) – Indicates when a packet has been detected on the Ethernet port. NOTE: Flashing of
this LED does NOT necessarily mean that a packet addressed to this Etherlon module has been received, just
that a packet has been detected on the Ethernet network.

ERR LED (Red) – Indicates a possible error condition.

Always On: A diagnostic error has been detected. Press the “RESET” button. If the “ERR” LED now

stays off, the EEPROM contained invalid data and has been reinitialized. Any non-volatile
information must be re-entered by using the EtherPlug program.

If the LED stays on solid, a hardware

problem is indicated. Contact technical support for assistance.

Slow Flash: (once per second) L

ON

W

ORKS

configuration information is insufficient. Using a

network management tool, re-commission the internal router nodes (and optionally, the Control
Neuron Processor node).

Quick Flash: (twice per second) IP address configuration is insufficient. Using EtherPlug, configure

the IP addressing parameters.

LonWorks NETWORK Connections

Screw Terminal and RJ-45

ASYNC Connector

Used with EtherPlug to access IP
address parameters

RESET Button

CSVC Button Initiates Service Request from

Control Neuron

RSVC Button Initiates Service Request from

Router

PWR LED Indicates correct input power
ERR LED

Indicates an error condition
(see below)

ACT LED

Indicates LonWorks packet
activity in router