CONDITION

POSSIBLE CAUSE

FIX

OPERATOR WILL NOT
RESPOND TO ANY
COMMANDS

A) No power

➤ Verify primary line voltage (120 Vac, 60 Hz) is present at terminals L1 &

L2.
The LED will fl ash when power is present.

B) Stop circuit not complete

➤ Verify Stop Button input (terminals 3 & 5) is properly wired and stop

button is not stuck.

C) Stuck button on 3-button

control station

➤ Verify that all buttons are actuating freely and releasing properly.

D) Interlock input activated

➤ Verify jumper is located at terminals 3 & 4 if interlock is not present.
➤ Verify interlock is properly wired and not activated.

E) Motor overload tripped

➤ Overload is internal within motor. Allow to cool and retry.

F) Accessory failure

➤ Attempt to close by holding the CLOSE button for more than 5 seconds. If

door closes, check accessory for proper wiring, polarity, connections or
damage.

➤ Verify photoelectric sensors are aligned or sensing edge is not activated.

G) Possible component failure

➤ Call Technical Support for assistance.

OPERATOR MAKES
NOISE BUT DOOR
DOES NOT MOVE

A) Clutch slipping

➤ Adjust clutch, see ADJUSTMENT section.

B) Brake not releasing

(if present)

➤ Verify brake assembly operation and wiring.

C) Door operation problem

➤ Disconnect trolley and check door for proper operation.

OPERATOR MOVES
IN THE WRONG
DIRECTION

OPEN and CLOSE button
wiring connection reversed

➤ Check 3-button control wiring.

DOOR DRIFTS AFTER
OPERATOR STOPS

A) Door not balanced properly

➤ Disconnect trolley assembly and check door for proper operation.

B) Clutch slipping

➤ Adjust clutch, see ADJUSTMENT section.

C) Brake not functioning

properly

➤ Check brake mechanism to ensure brake lever is free and brake pads are

engaging the brake disc.

DOOR OPENS/
CLOSES TOO FAR

Limits not adjusted properly

➤ Adjust limits. See ADJUSTMENT section.

DOOR REVERSES
UNEXPECTEDLY

Intermittent Entrapment
Protection Device activation

➤ Check all connections.

TTC NOT
FUNCTIONING

A) Monitored Entrapment

Protection Devices

➤ Check all connections. Verify photoelectric sensors are not blocked and the

sensing edge is not activated.

B) TTC temporarily disabled

➤ Close and Open the door. TTC will be re-enabled.

C) TTC not programmed

properly

➤ Reprogram TTC. See PROGRAMMING TTC section.

RADIO FUNCTIONALITY NOTE: Built in radio receiver compatible with all LiftMaster 315 MHz remote control devices.

NO RESPONSE

A) Remote control is not

programmed

➤ See PROGRAMMING REMOTE CONTROLS section.

B) Remote control not

compatible

➤ Obtain qualifi ed LiftMaster remote control device.

C) Low battery

➤ Replace battery.

REMOTE CANNOT BE
LEARNED

A) Low battery

➤ Replace battery.

B) Remote control not

compatible

➤ Obtain qualifi ed LiftMaster remote control device.

POOR RADIO RANGE

A) Low battery in remote

➤ Replace battery.

B) Antenna not confi gured

➤ See SETUP RADIO ANTENNA.

C) Ambient radio interference

or building structural issue

➤ Use EXTERNAL ANTENNA kit (see ACCESSORIES page).

Technical Support 1-800-528-2806