Single Loop Process Controller Instruction Manual

Introduction 7

Environmental Characteristics (Cont’d):
Transient Immunity (all circuits)

EMI Susceptibility

Enclosure Classification/Environment

Shock

Vibration

Drop and Topple

Safety Classification

ANSI C37.90a - 1974/IEEE Std 472- 974:
Ring Wave: 1.5 MHz, 3 kV, 60 pulses/s for 2.0 s

SAMA PMC 33.1-1978: Class 3-abc: no effect
at 30 V/m, at 27, 146, and 446 MHz

Panel Mounted Equipment: No enclosure rat-
ing. Designed to be installed in a user provided
panel or enclosure.

Rated for installation in a Pollution Degree 2
location per U.L. 508-1989/Controlled Environ-
ment
per CSA C22.2 No. 142-M1987. An
indoor, temperature controlled location (Control
Room or Shop Floor) where normally, only non-
conductive pollution occurs; however, tempo-
rary conductivity caused by condensation may
be expected.

Location in environments more severe than
those stated requires supplementary protec-
tion.

0.5 g

SAMA PMC 31.1-1978; point-to-point constant
displacement 0.05 in. (1.27 mm), 5 - 14 Hz: 0.5
g, 14 - 200 Hz.

SAMA PMC 31.1-1978; Tilt 30 degrees from
horizontal and fall freely to a hard surface, all
sides, front and back.

General Purpose: Complies with ANSI/ISA
S82.01-1988, Safety Standard for Electrical
and Electronic Test Measuring, Controlling and
Related Equipment; General Requirements
and S82.03-1988 Safety Standard for Electrical
and Electronic Test, Measuring, Controlling and
Related Equipment; Electrical and Electronic
Process Measurement and Control Equipment.

FM Approved: Nonincendive for Class 1, Divi-
sion 2, Groups A, B, C, & D.

Table 1-1. Specifications (Continued)

Item

Specification(s)