Single Loop Process Controller Instruction Manual

72 Analog Backup Controller

.

Table 6-4. Contact Input Module (CCI)

Title

Symbol

CCI

Datapoint

Default

Contact Input
(Display Only)

CCI

L000

0

Contact Input
Invert

IINV

L264

0

Tag Name

CITAG

A262

CCI0

Table 6-5. Contact Output (CCO) Module

Title

Symbol

CCO0

Datapoint

Default

Contact Output
(Display Only)

CCO

L024

0

Contact Output
Invert

OINV

L288

0

Tag Name

COTAG

A280

CCO0

Note

Although the Analog Backup Controller has a second CCO (CCO1),
it is not configurable for this control strategy.

Table 6-6. Controller Module (CON-0)

Title

Symbol

CON-0

Datapoint

Default

Control Alarm
Mode

AIX

B335

1

Control Action

RSW

L106

1

Reverse Valve

RSV

L109

0

Manual Fallback
Disable

MFD

L120

0

Alarm Limit 1

PL1

C103

100

Alarm Limit 2

PL2

C104

0

Alarm Dead Band

ADB

C105

2

Proportional Band

PB

C106

100

Reset Time

TR

C107

0