Single Loop Process Controller Instruction Manual

42 Configuration Parameters

4.2 Factory Standard Configuration

The instrument is shipped from the factory configured as summarized in

Table 4-2

.

If the state of the database is unknown, the instrument can be returned to the factory standard
configuration with two datapoint entries:

1.

Set B00 to 98 to default the database.

2.

Set B00 to 1 to start functioning as a Single Loop Controller.

If the unit is to be operated online, it must be installed as described in

Section 2, Installation

.

ANI0 (PV Input) and ANO0 (Output) must be connected, and the unit must have power applied.

Table 4-2. Factory Standard Configuration

Datapoint

Value

Attribute

B000

1

This value indicates Single Loop PID Controller operation.

C106

100

Proportional Band = 100%.

C107

0

No Reset (TR) action.

C108

0

No Derivative (TD) action.

B335

1

No Alarms.

C256

100

ANI0 Engineering Span Input (Process Variable [PV] Input) = 0% - 100%.

L416

0

ANI0 Input Voltage Range is 1 - 5 V.

L106

1

Reverse Switch is set so that the instrument output decreases as PV increases.

L115

0

Remote Setpoint Disabled indicates the setpoint value established in Local
mode remains in effect when the instrument is placed in Remote mode.

Displays

1. As configured: Display of Single Loop Controller, Analog Back-up Controller,
Ratio Controller, or Automatic Manual Station

2. Parameter 1 Display