Single Loop Process Controller Instruction Manual

Front Panel 29

3.3.2 Altering a Datapoint

The following procedure illustrates how to enter EMODE and use the configuration function to alter the
contents of datapoint B000 (B0) with a 97. Entering a 97 in B00 invokes the display test which strobes the
display matrix dots on and off at 5 second intervals (approximate). When off, a perimeter of dots still
remains lit.

Figure 3-11

and

Figure 3-12

are display test illustrations that support the procedure provided in

Table 3-3

. It should be noted that EMODE has a 20 second timeout if it is accessed and its functions (e.g.,

configure or display) are not used.

Figure 3-10. A1 PERCENT

Table 3-3. Procedures to Alter a Datapoint

Step

Press

Shift

Result

Press to

Locate

Target

Char.

Result

1

MODE

Puts instrument in EMODE.

2

If CONFIGURE does not appear, press F2.

3

F3

Displays entry line: POINT .
(If the prompt KEY? appears, see

Table 3-5

.)

4

B

Puts B on entry line: POINT .B.

5

.B

0

Shifts B and puts 0 on entry line: POINT .B0.

6

.B0

0

Shifts B0 and puts 0 on entry line: POINT .B00.

7

F3

Displays contents of B00 (0).

8

hold

.

locator

B00 contents shifted right; only locator point
remains on the entry line: B00 .

9

9

Puts 9 on entry line: B00 .9.

10

.9

7

Shifts 9 and puts 7 on entry line: B00 .97.

11

F3

Enters 97 in B00 to start the display test.