A.O. Smith AHD 290 User Manual

Page 56

Advertising
background image

56

1.3

Operating menu

E0: Factory default

If the system does not function as expected, even though the set points have

been adjusted, and the cause is impossible to locate, it is

recommended to note down the settings in the schedule. Thereafter the set point

must be adjusted to 1 and wait until the control returns to standard settings. Now

all the set points have been changed to the factory default. It is now possible to

start all over and adjust the set points.

Factory setting: 0

E2: T9 set temperature

This sensor is able to control the relay R9, which will be activated when the set-

point E2 is reached. The R9 relay can be used to control the three way damper

of the exhaust air. This three way damper can supply the living area with cool air,

if the room temperature reach the setpoint E2. For this function you will need a

separate sensor, which is not a within the standard delivering. The sensor shall

be connected to the control panel. For access to the control panel you have to

dismantle the top of the machine.

E2 can be set between 10-30°C

Factory setting: 21°C

E8: Disinfection function ON/OFF

By setting the point to 1, the electric cartridge will provide 65°C hot water, once a

week, in order to disinfect the tank (legionella protection function).

Factory setting: 0

E9: Operating in cold surroundings ON/OFF

If the setting is 0, the heat pump will run as long as there is a need of heat (=

exhaust air-operation).

Using the heat pump when taking the admission air from e.g. the cellar, there

is an option of making the compressor stop in case the room is getting to cold.

Instead, the electric heater will heat the water. The function is activated when the

value has been set to 1 (= circulating air-operation).

It is also possible to automatically let the electrical heater help heating the water

when the intake air temperature is below the temperature set in E10. The function

is activated when the value has been set to 2 (= fresh air operation). If the value

is 0, the function is not active.

Factory setting: 0

E10: Operating in cold surroundings

When activating the function menu E9, the temperature at which the compres-

sor will stop, or the heater will assist, may be set. The temperature is adjustable

between –10 and +10°C.

Factory setting: -5

E15: Hygrostat / stop unit

If the value is 0, the speed of the fans will change to 3 when the relative humidity

is above the preset value of the hygrostat. If the value is 1, the unit will stop when

the clips 25 and 26 are short-circuiting.

Factory setting: 0

E16: Min. airflow

This value shows the minimum speed at which the fan is permitted to run when

operating. Notice that the cooling system may be overloaded,

resulting a drop out of the high-pressure switch, if the value has been set too

high. The value should not be chosen higher than necessary, in order to secure a

minimal airflow through the cooling coil. Adjust this value between 0-100%.

Factory setting: 0