E17: Extended airflow ON

At 3rd speed, there is an option of making the unit step down automatically to

the 2nd speed, after a number of hours, by adjusting to set 1. If the setpoint is

adjusted to 0, the unit will run at the 3rd speed until a lower speed has been

selected manually.

Factory setting: 0

E18: Hour

If automatic step-down at 3rd speed is in use, the number of hours at which the

unit is to operate with forced air, may be adjusted here. The setpoint may be

adjusted between 1 - 10 hours.

Factory setting: 3

E19: Extra function

If the setpoint is 1 the extra function will be activated as soon as T9 reach the

setpoint (se E2). If the setpoint is 0, the function will be out of order.

E21: TX set

In order to avoid high operating pressures in the cooling system, the system out-

put must be reduced for the remaining part of the heating period. This parameter

indicates the water temperature at which the reduction should start. It may be set

to 0-55°C.

Factory setting: 50

E23: Tmop

This value indicates the maximum permitted evaporation temperature. This pre-

vents overloading of the compressor system at high ambient

temperatures.

Adjust this value between 0-25°C.

Factory setting: 25

E25: Vent level 2

If an extended period of extraction from the building is wanted, it is possible to

change to level 2. The fan will now run until another level has been selected.

This option is used to set the speed at which the fan should run, when level 2 is

selected. Please note that this setting also sets the maximum fan speed when

running in level 1. The speed may be set to 0-100%.

Factory setting: 100

E26: Vent level 3

If extraction from the building at a specific length of time is required, it is possible

to change to level 3. The fan will now run for the set period. Thereafter the sys-

tem will return to level 2. This menu option is used to specify the speed at which

the fans should run when the set period has been chosen. Please note that this

setting also sets the maximum fan speed when running in level 1 The speed may

be set to 0-100%.

Factory setting: 100%

E27:

Available function. Must at all times be 1.

E45: dTair-set

Here it is possible to choose minimum cooling of the air, while heating the water.

The control will adjust the speed of the fan to make sure the air will be cooled at

the exact temperature chosen. In case the control needs to cool the air due to

technical reasons, the value will be controlled by the automatic function. When

requiring a higher fan speed, the value may be reduced. Remember though, the-

fan will run faster, using more energy, if the values are set to low.

Factory setting: 1