MOD 30ML Operation

SETUP

2-11

Table 6. Template Configuration (Cont’d)

Step

Step Description

Line 1

Line 2

Line 6

Entry Description

6C

Install Template

∇ move down to 6C1

NXT, PRV change step

INSTALL TEMPLATE

Installation verifies and loads the
template making it the active
database (changes state to RUN).

6C1

Installation of Template

∇ ∆ select YES (press again from
NONE returns you to Step 6C)

ENT loads template and displays
first runtime display.

INSTALL TYPE

NONE

Select NONE to exit installation.
Select INITCOLD to install and
RUN template using a cold start.
Select INITWARM to install and
RUN template using a warm start.

6C2

Configuration Request Failed

ACK acknowledges failure
message and changes to Step 6B.

CONFIG REQUEST

FAILED

Data base verification failed
because of some inconsistency in
database or an active shutdown
condition. To ACK failure, go to
DEV STAT level and set ACK SD
to Yes (Step 1B5).

6D

Template (Exit)

∆ moves up to Step 6

NXT, PRV change step

TEMPLATE


Table 7. System Template Configuration

Step

Step Description

Line 1

Line 2

Line 6

Entry Description

7A

System Device Tag

∇ ∆ change a character

NXT, PRV flash to change position

ENT enters new device tag.

NXT, PRV change step

SYSTEM

DEV TAG TEMP 100

Modify device tag using standard
set of characters. This tag identifies
instrument.

7B

System Scan Groups (Entry)

∇ moves down to Step 7B1

NXT, PRV change step

SYSTEM SCANGRPS

Scan groups 1 through 5 are user
defined intervals for loops. The
fastest group has the highest
priority. The lower numbered group
has a higher priority if the interval is
the same.

7B1

Scan Group 1 Interval

∇ ∆ changes interval, ENT enters

NXT, PRV change step

SCAN GROUP

1

0:00.100

Set group scan interval.
(50ms to 50:00.000 Hrs)

7B2

Scan Group 2 Interval

∇ ∆ changes interval, ENT enters

NXT, PRV change step

SCAN GROUP

2

0:00.000

Set group scan interval.
(0 to 50:00.000 Hrs)

7B3

Scan Group 3 Interval

∇ ∆ changes interval, ENT enters

NXT, PRV change step

SCAN GROUP

3

0:00.000

Set group scan interval.
(0 to 50:00.000 Hrs)

7B4

Scan Group 4 Interval

∇ ∆ changes interval, ENT enters

NXT, PRV change step

SCAN GROUP

4

0:00.000

Set group scan interval.
(0 to 50:00.000 Hrs)

7B5

Scan Group 5 Interval

∇ ∆ changes interval, ENT enters

NXT, PRV change step

SCAN GROUP

5

0:00.000

Set group scan interval.
(0 to 50:00.000 Hrs)

7B6

System (Tasks Exit)

∆ moves up to Step 7B

NXT, PRV change step

SYSTEM