Micromod MOD: 30ML Operation and Template Setup User Manual

Page 27

Advertising
background image

MOD 30ML Operation

SETUP

2-17

Table 8. User Compound Template Configuration (Cont’d)

Step

Step Description

Line 1

Line 2

Line 6

Entry Description


Steps 8E3A through F only presented when there is a remote setpoint input

8E3A

Local Setpoint Enable

∇ ∆ change value, ENT enters

NXT, PRV change step

LOCAL SETPOINT ENABLE

Enable or Disable a local setpoint
value

8E3B

Setpoint Ratio

∇ ∆ change value, ENT enters

NXT, PRV change step

SETPOINT RATIO DISABLE

Enable or Disable a remote
setpoint ratio value

8E3C

Setpoint Ratio Value

∇ ∆ change value, ENT enters

NXT, PRV change step

SETPOINT RATIO

1.000

Initial ratio value.
Auto balance calculation is:
(Active Setpoint - Bias) / Rem SP

8E3D

Setpoint Bias

∇ ∆ change value, ENT enters

NXT, PRV change step

SETPOINT BIAS DISABLE

Enable or Disable a remote
setpoint bias value

8E3E

Setpoint Bias Value

∇ ∆ change value, ENT enters

NXT, PRV change step

SETPOINT BIAS

0.000

Initial bias value.
Auto balance calculation is:
Active Setpoint - (Rem SP * Ratio)

8E3F

Setpoint Balance

∇ ∆ change value, ENT enters

NXT, PRV change step

SETPOINT BALANCE AUTO

RAT

AUTO RAT, Ratio value calculated
to balance transition to remote.
STANDARD, Ratio and Bias use
the operator values.
AUTO BIA, Bias value calculated to
balance transition to remote.


Setpoint (Cont’d)

8E4

Setpoint Low Limit

∇ ∆ change value, ENT enters

NXT, PRV change step

SETPOINT LO LIMIT 0.000

Setpoint values to the PID
algorithm are limited to this number
or above.

8E5

Setpoint High Limit

∇ ∆ change value, ENT enters

NXT, PRV change step

SETPOINT HI LIMIT 100.000

Setpoint values to the PID
algorithm are limited to this number
or below.

8E6

Setpoint Restart Mode

∇ ∆ change value, ENT enters

NXT, PRV change step

RESTART SP

MODE PREVIOUS

Previous (requires setting initial SP
Mode), Local or Remote
Local only for Master Controller.

8E7

Setpoint Initial Mode

∇ ∆ change value, ENT enters

NXT, PRV change step

INITIAL SP

MODE LOCAL

Local or Remote
Local only for Master Controller.

8E8

Setpoint Restart Value

∇ ∆ change value, ENT enters

NXT, PRV change step

RESTART SP

VAL PREVIOUS

Previous (enter an Initial Value) or
Preset (enter a Restart Value).

8E9

Setpoint Restart Preset Value

∇ ∆ change value, ENT enters

NXT, PRV change step

RESTART VALUE

0.0

Enter restart value for setpoint.

8E10

Setpoint Initial Value

∇ ∆ change value, ENT enters

NXT, PRV change step

INITIAL VALUE

0.0

Enter initial value for setpoint.

8E11

Setpoint Tracking

∇ ∆ change value, ENT enters

NXT, PRV change step

SETPOINT TRACK DISABLE

Enable or Disable
When active, setpoint tracks input
while in manual.

8E12

Setpoint (Exit)

∆ moves up to Step 8E

NXT, PRV change step

COMPOUND