MOD 30ML Operation

SETUP

2-12

Table 7. System Template Configuration (Cont’d)

Step

Step Description

Line 1

Line 2

Line 6

Entry Description

7C

System Passwords (Entry)

∇ moves down to Step 7C1

NXT, PRV change step

SYSTEM PASWORDS

The passwords set here will restrict
access to tuning and configuration
features.

7C1

Tune Passwords

∇ ∆ changes number, ENT enters

NXT, PRV change step

TUNE PASSWORD

0

Enter a number required to access
tuning parameters.

7C2

Configure Passwords

∇ ∆ changes number, ENT enters

NXT, PRV change step

CONFIG PASSWORD

0

Enter a number required to access
configuration parameters.

7C3

Access Timeout

∇ ∆ changes number, ENT enters

NXT, PRV change step

ACCESS TIMEOUT

0

0-54 minutes; 0=infinite
The time in minutes that the tune
and configure access levels will
timeout and return to the operate
level after last keyboard activity.

7C4

System (Passwords Exit)

∆ moves up to Step 7C

NXT, PRV change step

SYSTEM

7D

System Alarms (Entry)

∇ moves down to Step 7D1

NXT, PRV change step

SYSTEM ALARMS

Alarm indication rates apply to
light, display and beeper. Alarms
are: unacknowledged diagnostics,
high or low process and deviation
conditions, and input quality.

7D1

Diagnostic Flash/Beep Rate

∇ ∆ change value, ENT enters

NXT, PRV change step

DIAGNSTC RATE FAST

FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec

7D2

Diagnostic Flash

∇ ∆ change value, ENT enters

NXT, PRV change step

DIAGNSTC FLASH OFF

OFF = flashing is disabled
ENABLE = flash display (LED
always flashes for diagnostic)

7D3

Diagnostic Beep

∇ ∆ change value

DIAGNSTC BEEP ENABLE

OFF = beeping is disabled
ENABLE = beep for diagnostic

7D4

Minimum Low Alarm Priority

∇ ∆ change value, ENT enters

NXT, PRV change step

MINIMUM LOW

PRI

100

All process alarms with priority >=
this value (2 - 255) are considered
LOW priority for display purposes.

7D5

High Priority Process Alarm Flash/

Beep Rate

∇ ∆ change value, ENT enters

NXT, PRV change step

HIGH PRI RATE

FAST

FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec

7D6

High Priority Process Alarm Flash

∇ ∆ change value, ENT enters

NXT, PRV change step

HIGH PRI FLASH

OFF

OFF = flashing is disabled
ENABLE = flash display on alarm

7D7

High Priority Process Alarm Beep

∇ ∆ change value, ENT enters

NXT, PRV change step

HIGH PRI BEEP

OFF

OFF = beeping is disabled
ENABLE = beep on alarm

7D8

Low Priority Process Alarm Flash/

Beep Rate

∇ ∆ change value, ENT enters

NXT, PRV change step

LOW PRI RATE

SLOW

FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec

7D9

Low Priority Process Alarm Flash

∇ ∆ change value, ENT enters

NXT, PRV change step

LOW PRI FLASH

OFF

OFF = flashing is disabled
ENABLE = flash display on alarm