2-14

Table 8. User Compound Template Configuration (Cont’d)

Step

Step Description

Line 1

Line 2

Line 6

Entry Description

Volt, Milliamp and Millivolt Inputs Only:

8D4
(V, mA)

Process Input Low Signal

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP LO SIGNL

1.00
4.00
0.00

0% value in input units.
Volts
milliamps
millivolts

8D5
(V, mA)

Process Input High Signal

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP HI SIGNL

5.00
20.00
100.00

100% value in input units.
Volts
milliamps
millivolts

8D6
(V, mA)

Process Input Linearization

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP LINEARZT LINEAR

LINEAR,
MOD SQRT modified square root,
MOD SQR modified square,
SQ ROOT square root, or
SQUARE

Resistance Inputs Only:

8D4
(Res.)

Process Input Resistance Range

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP RES RNGE LOW

LOW (built-in = 0 to 55 ohms)
NORMAL (built-in = 0 to 430 ohms)

8D5
(Res.)

Process Input Low Signal

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP LO SIGNL 0.00

0% value in ohms.

8D6
(Res.)

Process Input High Signal

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP HI SIGNL 4000.00

100% value in ohms.

8D7
(Res)

Process Input Nominal Resistance

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP NOM RES 0.00

Resistance produced by RTD in
ohms at zero degrees Celsius.
Ranges are: 2-Wire module (0 to
4000), 3-Wire module (0 to 400),
BI AIN (0 to 430).

8D8
(Res.)

Process Input Leadwire Resistance

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP LW RES

0.00

Leadwire resistance in ohms.
Values that cause the sum of the
leadwire resistance and the input to
exceed maximum resistance will
cause an overrange error.

Thermocouple Inputs Only:

8D4
(TC)

Process Input Thermocouple Type

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP TC TYPE TC TYPEK

Types are: B, E, J, K, N, R, S, T.

8D5
(TC)

Process Input Temperature Scale

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP TEMPSCAL CELSIUS

Celsius
Kelvin
Rankine
Farenheit

8D6
(TC)

Process Input Zero

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP ZERO

0.00

Specify zero calibration value in
result units.

8D7
(TC)

Process Input Span

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP SPAN

1.00

One is nominal. Specify span
calibration value in result units.