MOD 30ML Operation

SETUP

2-18

Table 8. User Compound Template Configuration (Cont’d)

Step

Step Description

Line 1

Line 2

Line 6

Entry Description

8F

Control Type (Entry)

∇ moves down to Step 8F1

NXT, PRV go to 8F, 8D

CTAG01 CONTROL

8F1

Control Algorithm Type

∇ ∆ change value, ENT enters

NXT, PRV change step


Values are: ESPO, PMPO, EMPO,
EOEO, ESEO, EMEO, EOOE, EOPE,
EOEE, EOOO, OSOO, PSOO, ESOO,
OMOO, PMOO, EMOO, EOPO, PSPO

CONTROL ALGO TYP ESPO

Gain (1st Character):
O

=

Off

P = On Process
E = On Error
Reset (2nd Character):
O

=

Off

S = Standard
M = Micro-Scan
Pre-Act (3rd Character):
O

=

Off

P = On Process
E = On Error
Manual Reset (4th Character):
O

=

Off

E = Enabled

8F2

Control Action

∇ ∆ change value, ENT enters

NXT, PRV change step

CONTROL ACTION REVERSE

Reverse (output decreases as
process rises above setpoint),
Direct (output increases as process
rises above setpoint)

8F3

Gain

∇ ∆ change value, ENT enters

NXT, PRV change step

GAIN

0.01

0.01 to 125.0
Proportional response in a fixed
gain controller.

8F4

Reset

∇ ∆ change value, ENT enters

NXT, PRV change step

RESET

0.01

0.01 to 125.0
Reset in repeats per minute.

8F5

Preact

∇ ∆ change value, ENT enters

NXT, PRV change step

PREACT

0.00

0.00 = Off
0.07 to 32 preact time base value.

8F6

Control Input Filter Type

∇ ∆ change value, ENT enters

NXT, PRV change step

CONTROL FILTYPE NONE

NONE = No low pass filter (last
sampled value is input value)
PRE AUTO = Preact Auto type low
pass filter based on derivative time
and task execution rate.
PRE USER = Filter time applied to
derivative (on process error) signal
before use in PID.
PROCUSER = Filter time applied
to process (on process error) signal
before use in PID.

8F7

Filter Value

∇ ∆ change value, ENT enters

NXT, PRV change step

FILTER

0.00

Filter Time in minutes. Small
values maintain recent input and
large values maintain previous
input.

8F8

Control Manual Reset Balance Type

∇ ∆ change value, ENT enters

NXT, PRV change step

CONTROL MR

TYPE NONE

NONE = No manual reset balance.
PRCDLESS = Procedureless
manual reset (value recalculated
on a transfer to auto). Calculation
compares output and error signals
(MR = output - (gain * error).