Micromod MOD: 30ML Operation and Template Setup User Manual

Page 30

Advertising
background image

MOD 30ML Operation

SETUP

2-20

Table 8. User Compound Template Configuration (Cont’d)

Step

Step Description

Line 1

Line 2

Line 6

Entry Description

8G

Output (Entry)

∇ moves down to Step 8G1

NXT, PRV change step

CTAG01 OUTPUT

8G1

Output Slot Position

∇ ∆ change value, ENT enters

NXT, PRV change step

OUTPUT

SLOT

OUT CH 1

NONE, OUT CH 1, OUT CH 2,
S01 to S11. Only available outputs
are listed.

8G2

Output Low Signal

∇ ∆ change value, ENT enters

NXT, PRV change step

OUTPUT

LO SIGNL 4.0

0% of the output range.

8G3

Output High Signal

∇ ∆ change value, ENT enters

NXT, PRV change step

OUTPUT

HI SIGNL 20.0

100% of the output range.

8G4

Output Display Format

∇ ∆ change value, ENT enters

NXT, PRV change step

OUTPUT

DISP FMT FLOAT 3

Float 0 = x, Float 1 = x.x
Float 2 = x.xx and so forth to
Float 6 = x.xxxxxx

8G5

Output Low Limit

∇ ∆ change value, ENT enters

NXT, PRV change step

OUTPUT

LO LIMIT -10.0

PID output limited to this number or
above.

8G6

Output High Limit

∇ ∆ change value, ENT enters

NXT, PRV change step

OUTPUT

HI LIMIT 110.0

PID output limited to this number or
below.

8G7

Output Restart Type

∇ ∆ change value, ENT enters

NXT, PRV change step

RESTART TYPE

PREVIOUS

PREVIOUS, PRESET

8G8

Output Initial Value

∇ ∆ change value, ENT enters

NXT, PRV change step

OUTPUT

INIT VAL 0.0

8G9

Output (Exit)

∆ moves up to Step 8G

NXT, PRV change step

COMPOUND

8H

Alarms (Entry)

∇ moves down to Step 8H1

NXT, PRV change step

CTAG01 ALARMS

8H1

Process Value Alarms

PV ALARMS

8H1A

Process Value Alarm 1 Type

∇ ∆ change value, ENT enters

NXT, PRV change step

NXT goes to Alarm 2 from NONE

PV ALM 1 TYPE

NONE

NONE,
HIGHHIGH (>=), HIGH (>=),
LO (<=), LOW LOW (<=).

8H1A1 Process Value Alarm 1 Trip Value

PV ALM 1 TRIP VAL 0.000

Value where input will cause alarm
to trip.

8H1A2 Process Value Alarm 1 Hysteresis

PV ALM 1 HYSTRSIS 2.000

Absolute offset to clear alarm.

8H1A3 Process Value Alarm 1 Priority

PV ALM 1 PRIORITY 1

0 to 255. 0 = suppress unack.

8H1A4 Process Value Alarm 1 Digital Output PV ALM 1 DIG OUT NONE

NONE, S01 through S11

8H1B

Process Value Alarm 2 Type

Same as Alarm 1

PV ALM 2 TYPE

NONE

NONE, HIGHHIGH, HIGH, LOW,
LOW LOW

8H1C

Process Value Alarm 3 Type

Same as Alarm 1

PV ALM 3 TYPE

NONE

NONE, HIGHHIGH, HIGH, LOW,
LOW LOW

8H1D

Process Value Alarm 4 Type

Same as Alarm 1

PV ALM 4 TYPE

NONE

NONE, HIGHHIGH, HIGH, LOW,
LOW LOW

8H1E

Process Value Alarms (Exit)

∆ moves up to Step 8H1

NXT, PRV change step

ALARMS