be equalized. Consult your battery manufacturer or read the battery manual when you try to
equalize your batteries. Disconnect any DC load connected to the battery, as during
equalization mode, the charger will produce 16V to the batteries. You must monitor the
battery specific gravity throughout the equalization to determine the end of the equalization
cycle.

When EQ mode is set to ON, the unit will charge batteries in one full cycle before it starts to
equalize the battery. Check the battery electrolyte level. If necessary, refill with distilled water
only. All cells should have similar electrolyte levels. If distilled water is added, batteries must
undergo a complete charge cycle. The charger cannot determine when to terminate the
equalization of the battery. A 1 hour time-out is intended as a safety feature to terminate the
equalizing process. You can re-activate the EQ mode by setting it ON again as necessary
after checking batteries manually.

Optional Battery Temperature Sensor Feature:

Optional Battery Temperature Sensor KISAE Part Number #BTS-10K is highly recommended
to be used with the charger to protect your battery and provide better charging voltage accuracy.
The battery temperature sensor senses the battery temperature and makes adjustments to the
charging voltage.

Battery Charging Voltage Adjustment from 25 °C normal setting

Battery
Temperature

Flooded and GEL type

AGM type

< 25 °C

+ 0.027 V /°C

+ 0.021 V /°C

25 °C

0 V

0 V

> 25 °C

- 0.027 V /°C

- 0.021 V /°C

Note: The charger will terminate battery charging when the BTS senses the battery

temperature reaching 60 °C. It will not continuously make voltage adjustments when the
battery temperature drops to below 0 °C.

Understanding the Error Codes

Error Code on

Display

Condition Corrective

Action

Fault: E01

Low Battery

Battery voltage is too low
and unit has shutdown

Recharge battery immediately and
restart unit.

Fault: E02

High Battery

Battery voltage is too high
and unit has shutdown

Check battery voltage or determine if
any external charger with high voltage
output is connected to the battery bank

Fault: E03

Temp Protect

Internal temperature is too
high and unit has shutdown

Check if any object has blocked the air
flow of the unit. Check environmental
temperature. The unit will restart when
the internal temperature has reduced
to about 50 °C.

Fault: E04

AC Over Load

Inverter AC Output has
overload

Check AC load connected and restart
the unit.

Fault: E05

Short Protect

Inverter output is short
circuited and has shutdown

Check load connected to the AC
output and restart the unit.

Fault: E06

INV Over Load

Inverter output voltage is too
high or too low and has
shutdown

Check unit and load and restart the
unit.

Fault: E08

BTS Protect

Battery temperature is high
and warning occurs. Unit will
shutdown shortly.

Check battery. Check ventilation in
battery compartment. Check
environmental temperature.