6. TROUBLESHOOTING

To troubleshoot the unit, please note the error code displayed on the main unit and review
“Understanding the Error Codes” in section 4.

Problem Symptom

Solution

Condition: Inverter setting is set to Off, AC source is available

Unit is turned Off

Turn unit ON by following the instruction in
Section 4

AC source is not available

Check AC source.
Check AC input branch breaker is off
Check AC connection between the AC
source and the unit

AC Input breaker is turned
off or tripped

Check AC Load and reset AC Input breaker

No AC Output.
Charging LED
is off.

No DC power to unit


Battery voltage is low
(<7Vdc)

Check DC fuse, DC Disconnect switch (if
installed) and check if Branch breaker is
either blown or turned OFF
Use a separate charger to boost battery
voltage to above 7V and unit can be
restarted.

No AC output.
Fault LED is
on

30A Circuit Breaker is
tripped and check fault code

Check load and reset the AC breaker and
verify the error condition and make
correction.

Condition: Inverter setting is set to On, AC source is not available

Unit is turned Off

Turn unit ON by following the instruction as
in Section 4

No AC Output.
Battery Power
LED is off

No DC power to unit


Battery voltage is low
(<7Vdc)

Check DC fuse, DC Disconnect switch (if
installed) and check if Branch breaker is
either blown or turned OFF
Use a separate charger to boost battery
voltage to above 7V and unit can be
restarted.

AC breaker connected
between the Unit AC Output
to load is turn off or tripped

Switch on or reset breaker

No AC Output.
Battery Power
LED is on

Check AC Load Sense
setting. AC Output power
consumption is lower than
the AC Load

Decrease AC load sense power level or
increase AC load connected to AC Output.

No AC output.
Fault LED is
on

Check error code

Verify the error condition and make
correction.

Advertising