The combustion air baffle is not factory set – Lanair MX300 User Manual

Page 32

Advertising
background image

Section 11 - Burner Start-Up Procedure

28

15. When using the by-pass regulator adjust the fuel pressure gauge on the left side of the

burner to read.

NOTE:

NOTE: When using the metering pump the fuel flow is determined by the pump. Pressures
may not be the same as shown above.

Adjust the thumb screw on the fuel bypass regulator clockwise to increase pressure,

and counter clockwise to decrease pressure to the burner. The oil pressures listed above are a
starting point, you may need to adjust from there when VISUALLY SETTING THE FLAME
(See page 29-31, flame adjustment).

16. Adjust the barometric damper to obtain a draft of -.06 W.C. while the heater is hot and

operating.

NOTE: It is VERY IMPORTANT that the barometric damper is set to the required settings to
ensure the natural draft of exhaust gases (see section 4).

17. Depending on the type of fuel used, the elevation, temperature, and oil viscosity, the

combustion air baffle will need to be adjusted for optimum performance (See page 29-
31, flame adjustment).

18. When the room thermostat setting is met

the burner will shut off, but the fan will con-
tinue to operate until the cabinet tempera-
ture drops to 90º F.

The combustion air baffle is NOT factory set

!

Clockwise:
Increase fuel
pressure

Counter
Clockwise:
Decrease fuel
pressure

Fuel By-Pass Regulator
Not used with the optional Metering Pump

Thumb Screw

QUESTIONS?... Contact Customer Service at 1-888-370-6531 M-F 8:00 am- 4:15 pm CST

No. 1 & No. 2 Fuel Oil

Approved Waste Oil

Model MX-250

2.25 (2-1/4) - 2.5 (2-1/2)LBS.

2.5 (2-1/2) - 2.75 (2-3/4) LBS.

Model MX-300

3 - 3.25 (3-1/4) LBS.

3.5 (3-1/2) - 3.75 (3-3/4) LBS.

Advertising
This manual is related to the following products: