Section 13 - Service / Maintenance

QUESTIONS?... Contact Customer Service at 1-888-370-6531 M-F 8:00 am- 4:15 pm CST

32

DAILY

s Check fuel supply

tank level (pre-strain
all fuels).

s Check vacuum gauge

reading on suction
line. See Section 19.

s Check atomizing air

pressure at the air fil-
ter/ regulator. Set to
18 psi. Drain water
from the bowl if nec-
essary

s Check the fuel pres-

sure gauge on the
burner. Set to the
correct pressure for
the fuel being used.

s Visually inspect

flame. Adjust accord-
ingly. NOTE: Wear
adequate eye, face
and breathing pro-
tection.

s Check draft using a

manometer. Set draft
to -.02 cold, -.06 hot.

s If heater is not to be
used for more than
48 hours (overnight)
flip the pre-heater
rocker switch off
(light off ).

WEEKLY

s Drain water/ anti-

freeze from the fuel
supply tank.

s Check the air pres-

sure setting on the
primary air regulator.
Set to 30 psi.

s Drain water from the

air pressure supply
line drain leg and pri-
mary regulator.

s Inspect the combus-

tion, ash build-up
and flame.
NOTE: Wear ade-
quate eye, face and
breathing protec-
tion.

MONTHLY

s Check combustion

chamber and heat
exchanger. Clean if
neccessary. Inspect
fire brick.
NOTE: Wear protec-
tive clothing, ade-
quate eye, face and
breathing protec-
tion. Do not breathe
dust from the com-
bustion chamber.
Wash thoroughly
with soap and
water after cleaning
chamber.

s Clean the chimney,

chimney connector
and barometric
damper.

s Clean pump strainer,

suction line strainer
and pick-up tube
strainer (pp 38).
NOTE: Always prime
pump after cleaning
strainers.

s Check for dirt build-

up on the combus-
tion blower wheel.
Keep wheel clean.

ANNUALLY

(Season Shut Down)

s Shut off main power

supply to heater.

s Perform monthly

service/maintenance.

s Flip air/fuel pre-

heater switch off.

s Shut off air supply.

s Remove air/fuel pre-

heater assembly.
Disassemble and
clean (pp. 34, 35).

s Remove air turbula-

tor and clean (pp. 33)

s Replace nozzle and

quad ring (pp. 34, 35,
39)

s Replace Ignitor (pp

39).

s Adjust turbulator (pp

39).

s Lubricate all motors

following specifica-
tions on the motor
rating plate.

s Clean fuel pump

strainer (see pp 38).

s Drain and clean fuel

supply tank.

s Clean combustion

blower, axial fan
blades and fan cage

MX SERIES HEATER SERVICE / MAINTENANCE SCHEDULE