Control board programming and features (continued), Relay drive troubleshooting leds, Troubleshooting leds – LiftMaster SL575 Heavy-Duty Commercial Slide Gate Operator User Manual

Page 26

Advertising
background image

26

LED Code

Diagnostic Meaning

Cleared By

Flashed

OFF

Normal

operation

N/A

1

Single entrapment sensed

Control Input

2

Double entrapment

Hard Input*

3

Failed or no hall

Removal of

effect

sensor

problem

4

Exceed maximum motor

Hard Input*

run

time

5

Limit fault

Control Input

6

Loss of communications

Removal of

between master and

problem

second during run mode

On No

Motor not learned

Completion

Flash

of

Motor

Learn Routine

* Hard inputs include open override, close override and

stop inputs.

LED

LED

NAME

DESCRIPTION

RELAY DRIVE TROUBLESHOOTING LEDS

There are 5 troubleshooting LEDs on relay drives K1 through K5. These LEDs will be illuminated when the microcontroller relay drive is
activated.

D6

Contactor A

On when Contactor A is activated

D5

Contactor B

On when Contactor B is activated

D4

SAM

On when SAM relay is activated

D3

Lock

On when Mag Lock relay is activated

D2

Alarm

On when Alarm Relay is activated

TROUBLESHOOTING LEDS

There are 9 troubleshooting LEDs.

D11

Radio

On when Radio switch is activated

D13

Shadow

On when Shadow Loop is activated

D15

Hard Close

On when Close switch is activated

D17 (Green)

Stop

On when Stop switch is not activated

D19

Soft Open

On when Open switch is activated

D21

Hard Open

On when Open switch is activated

D24

Interrupt (Safety) Loop

On when Interrupt/Safety Loop activated

D29

Obstruction Open

On when Edge is activated or when Photo Eye
Beam is broken

D31

Obstruction Close

On when Edge is activated or when Photo Eye
Beam is broken

FORCE CONTROL

Set the force control pot such that the unit will complete a full
cycle of gate travel but can be reversed off an obstruction without
applying an unreasonable amount of force. On most operators
this will be around the middle of the range.

NOTE: For LED location refer to illustration on previous page.

DIAGNOSTICS (LEDS AND CODES)

There are three diagnostic LEDs. Two red LEDs (OLS, CLS) are
indicators for the open and close limits. The LEDs are illuminated
when the limit switch contacts are closed.

The third amber LED (DIAG) is used to blink out diagnostic
codes. The number is the count of the number of times the LED
is on in an 8 second period. The LED is on for approximately 1/2
second and repeats every second until the number is reached.
There will be a pause following each pulse cycle (1-6 pulses) to
differentiate between the different diagnostic codes.

CONTROL BOARD PROGRAMMING AND FEATURES (CONTINUED)

Max

Min

Force Control

LED

LED

NAME

DESCRIPTION