Open area protection, Ceiling sampling – System Sensor Pipe Installation User Manual

Page 12

Advertising
background image

User Guide: Aspirating Smoke Detector Pipe Installation

12

Open Area Protection

Ceiling Sampling

In typical ceiling installations, the pipe network is suspended

from 1" to 1 ft. (25 mm to 300 mm) below the ceiling level in the

protected area unless otherwise specified by local codes and

standards. This type of installation is the most common. It could

be used in offices, warehouses, equipment rooms and a variety

of other types of installations. PipeIQ can also help provide

guidance for the design.

Frequently Asked Question – How do I design for
a peak ceiling?

When designing peak ceiling applications, the spacing

requirements of NFPA-72® apply. A sample port shall be

provided within 36" from the center of the peak on both sides.

The next sample port from the center shall comply within the

design parameters of VEWFD, EWFD or SFD. If stratification

could potentially occur, it is recommended to also provide

sample ports along the wall.

Adjacent sample port shall

be located based on spacing

requirements. (VEWFD, EWFD, SFD)

Air sampling pipe located 3 ft.

from the center of the peak

on both sides.

Sampling pipe

network -Typ.

Sample port -Typ.

FAAST Detector

3 ft.

Sampling Ports

Figure 13: Peak ceiling sampling design.

Figure 12: Ceiling sampling.