Object protection – System Sensor Pipe Installation User Manual

Page 14

Advertising
background image

User Guide: Aspirating Smoke Detector Pipe Installation

14

Object Protection

Cabinet Sampling

Equipment cabinet sampling may be accomplished in two

ways: pipe networks and sampling ports can be installed di-

rectly inside the equipment cabinet, or directly over the

equipment cabinets being monitored if the cabinets have

ventilation grills.

In-Cabinet Sampling

For in-cabinet sampling, capillary tubes can be used to enter

the equipment cabinet. The capillary tube is connected to the

pipe network via a tee connection with an adapter. The

maximum length of these capillary tubes is 26 ft. (8 m).

PipeIQ can help create an appropriate design.

An alternate to capillary tubes is a rigid drop tube. In this

application, the pipe network is run over a row of cabinets and

drop tubes are run down to each cabinet. This tube or pipe

should be less than or equal to the network pipe diameter and

is connected to the top of the cabinet and to the pipe network

via a tee connection. The pipe could also come up from under

a floor void in to a cabinet.

Cabinets with extractor fans may cause sampling problems

when the sample port is on the top of the cabinet. The

extractor fan creates a low pressure area within the cabinet that

can stop air from being drawn into the detector system at the

sampling port. This type of installation must be checked care-

fully for proper sampling operation. This can be accomplished

using canned smoke at the sample port location.

Above-Cabinet Sampling

In above-cabinet sampling, the pipe network should be installed

directly over the cabinets that will be protected. Sampling ports

are placed over the cabinet ventilation grills. Ports should be

oriented so that they face into the air stream coming from the

cabinet. If there is more than one exhaust from a cabinet, a

sampling port should be installed over each opening.

NOTE: With either application, it is best to locate the sampling

port in the path of the air flow near the top of the cabinet.

Figure 18: In-cabinet sampling.

Figure 19: Above-cabinet sampling.

Top View of Cabinet

Advertising