User Guide: Aspirating Smoke Detector Pipe Installation

9

½ S

½ S

½ S

½ S

½ S

½ S

S

S

S

S

S

S

Regulatory Requirements

Local codes and regulations can determine the size and

spacing between the sample ports in a network, making them

a critical part to any pipe design. These requirements change

depending on the type of environment being monitored. Local

codes and standards take precedence over any parameters

suggested by this document for FAAST systems.

Frequently Asked Question: How should the sample ports
be spaced?

Sample port spacing varies worldwide based on regulatory

standards. In the United States, sample ports shall be spaced

as defined per the requirements of NFPA. Each application

varies depending on the design. The requirements for sample

port square footage coverage is based on the detection

(Very Early Warning, Early Warning, or Standard) the design

is attempting to meet.

Transport times and obscuration levels required at each sample

port are as below:

Very Early Warning Fire Detection (VEWFD):

Sample port spacing: 200 sq. ft.

Transport time: 60 seconds from further port (includes test port)

Sample port sensitivity at pre-alarm: 0.2%obs/ft.

Sample port sensitivity at alarm: 1.0%obs/ft.

Early Warning Fire Detection (EWFD):

Sample port spacing: 400 sq. ft.

Transport time: 90 seconds from further port (includes test port)

Sample port sensitivity at alarm: 1.5%obs/ft.

Standard Fire Detection (SFD):

Sample port spacing: 900 sq. ft.

Transport time: 120 seconds from further port (includes test port)

Sample port sensitivity at alarm: 3.2%

Figure 9: Regulatory requirements.

This figure indicates the sample port spacing for each
classification requirement. The "S" indicates the maximum
distance allowed per sample port while "½ S" indicates
the maximum distance a sample port can be from a wall.
Each design will vary based on the shape of the building
but this template should be used as a starting point.

Design Classifications

Classification

Type

Area Per

Sample

Port

Maximum

Spacing

Between

Ports (S)

Maximum

Spacing

From Wall

(½ S)

VEWFD

200 sq. ft.

14 ft.

7 ft.

EWFD

400 sq. ft.

20 ft.

10 ft.

SFD

900 sq. ft.

30 ft.

15 ft.