System Sensor Pipe Installation User Manual

Page 19

Advertising
background image

User Guide: Aspirating Smoke Detector Pipe Installation

19

Basic Pipe Network Cleaning
and Maintenance Procedure

Periodic maintenance of the FAAST Fire Alarm Aspiration Sens-

ing Technology pipe network is recommended in environments

with high amounts of airborne particulate, or cold environments

where condensation may freeze on the sampling port and affect

pipe network performance. Annual maintenance of the pipe

network is recommended for all installations.

Low flow faults on devices which have been installed and oper-

ating normally for a period of time may signal the need for pipe

network cleaning.

Pipe Network Maintenance

During installation of the pipe network, it is recommended that

a valved tee fitting be installed 6 inches to 1 foot from the pipe

inlet so that the pipe entering the detector is not subject to any

flow of air during the pipe network maintenance. Forcing air in

to, or out of, the FAAST unit by any means other than the inher-

ent fan may cause damage to the device and nullify the device

warranty.

Prior to beginning pipe network maintenance:

• Place the device in isolate or disable mode, or power

down.

• Remove the pipe network from the device, or switch the

valve on a valved tee fitting to ensure that no air can be

force in to or out of the device

To perform pipe network maintenance:

• Affix a vacuum cleaner, or air compressor, to the end of

the pipe network or the entry in to the valved tee fitting.

• While the vacuum is running, use a dry brush or pipe

cleaner to swab out each sampling port in the pipe net-

work. Leave vacuum running for 2 min following last port

cleaning.

Post pipe network maintenance:

• Reconnect pipe network to the FAAST device or switch

the valved tee tap

• Remove the device from isolate or disable mode, or

reapply power to the FAAST

• Observe the air flow pendulum on the user interface. The

two green indicators should be near center underneath

the device’s power indicator. If a low condition existed

before maintenance, this condition should be clear after

maintenance (NOTE: if the device is set to latch in fault,

the device will need to be reset to clear the fault)

• If the low flow condition persists, perform another manual

check of the pipe network against the pipe layout report

generated by PipeIQ. Also, if the exhaust pipe is not

situated in the protected space the low/high flow condition

could be the result of differences in room pressures that

have changed do to open doors, windows or upgrades to

ventilation units.

Filter Maintenance

Filter maintenance is required only when a ‘Filter’ fault is indi-

cated by the FAAST unit. Perform the following procedure to

replace the filter assembly:

1. Remove power from the system.
2. Open the door on the right side of the device that covers

the LED system indicators.

3. Remove the plastic name card over the LEDs.
4. Remove the two screws holding the filter assembly into

the device.

5. Remove the filter assembly and replace it with a

new assembly.

6. Torque the two Phillips-head screws to 6in-lb (0.7 N-M)

or ¼ turn past “lightly snug’. DO NOT OVERTIGHTEN.

7. Replace the plastic name card over the LEDs.
8. Close the door and restore power to the system.