Drilling sample ports, Installation stages – System Sensor Pipe Installation User Manual

Page 7

Advertising
background image

User Guide: Aspirating Smoke Detector Pipe Installation

7

Drilling Sample Ports

Each port in a sampling pipe represents a smoke detection

location. Port placement and size are determined using the

PipeIQ software. Sample ports should be measured, marked,

and drilled before the network is installed. To prevent sampling

ports from being blocked by dust and dirt, place ports on the

bottom side of the sampling pipe, not the top side. This ensures

that any falling debris does not clog the sampling ports. This

port positioning should also be followed for voids in the ceiling

or floor.

The following guidelines should be followed when drilling the

sample ports in the pipe network.

• Ports must be drilled perpendicular (90 degrees) to the

pipe. If the drill is not held perpendicular, the port is not

round and not modeled properly in PipeIQ.

• Tapering the ports reduces dust collection at the

sample ports.

• Sampling ports must be drilled exactly at the positions

marked on the pipe with the exact size as determined by

the PipeIQ software.

• Ports must not be drilled through both sides of the pipe.
• Ports should be drilled with a slow speed drill with a sharp

drill bit. This minimizes dust and burrs entering the

pipe network.

It is good practice to blow compressed air through the pipe

after drilling to clear any debris before final connection to the

FAAST detector. Alternately, a shop vacuum can be used to

remove debris from the pipe network. Ensure that the pipe is

disconnected from the FAAST detector when vacuuming pipe.

Installation Stages

Table 3 lists the standard installation stages for an aspiration

pipe network.

STEP

ACTION

1

Verify design documents are accurate and obtain the size

and configuration of the pipes in the network.

Note: If PipeIQ was used to design the network, a bill of

materials can be generated from the application.

2

Mark off the area where the system is to be installed and

identify the location where the FAAST detector is to be

mounted.

3

Select and mark the locations for the pipe clips in

accordance with the design.

4

Install the FAAST detector in its permanent location.

(See Installation and Maintenance Guide for details.)

5

Mount the pipe clips according to the previous markings.

6

Dry mount and assemble the pipe network according

to the pipe network design documents. CAUTION: Do not

permanently connect the pipes at this time.

7

Measure and mark the sampling ports on the pipe

network. Make sure that the spacing of the sampling

ports is in accordance with the network design. Based

upon the application, ensure that the sampling ports are

at the correct orientation to the air flow, as recommended

in the section on network pipe design.

8

Modify the design documents to agree with the actual

network, if the physical network is different from the origi-

nal design, this new layout should be re-designed and

confirmed in PipeIQ prior to drilling sampling ports.

9

Verify the sampling port positions and orientations and

drill the sampling ports.

10

Drill and install end caps on all appropriate pipe ends.

11

When testing is complete and the system performance is

verified, permanently bond the pipe network together.

CAUTION: Never bond the pipes to the detector. The

detector inlet and outlet are tapered to accept the piping

without any bonding and provide an air tight seal.

12

Label all portions of the system according to local codes

and regulations. Pipe and Sampling Port labels are avail-

able – refer to the Accessories section.

13

If additional changes are made, ensure that design

documents are updated accordingly.

Table 3: Installation steps.

Advertising