Chapter 2 Specifications

2-3

2.2

Performance Specifications

2.2.1

Input Specifications

Input points

12 inputs with common line (source/sink input signal)

Rated input voltage

DC24V

Input voltage range

from DC20.4 to 26.4V

Rated input current

I0, I1, I6, I7:5mA/input (DC24V)
I2 to I5, I8 to I11: 7mA/input (DC24V)

Input impedance

I0, I1, I6, I7: 5.0 k

I2 to I5, I8 to I11: 3.4 k

Switching time at high status
(ON Time)

I0, I1, I6, I7: 35 µs + filter value
I2 to I5, I8 to I11: 40 µs + filter value

Switching time at low status
(OFF Time)

I0, I1, I6, I7: 45 µs + filter value
I2 to I5, I8 to I11: 150 µs + filter value

Isolation

Between input terminals: not isolated
Internal circuit: photocoupler isolated (isolation protection put to
AC500V rms)

Filtering: 3 possibilities
• none
• 3 ms
• 12 ms

I0 to I11

Input type

Type 1 (IEC 61131)

External load for I/O
interconnection

Not needed

Signal determination method

Static

Input cable length

3 m [118.11 in.] for compliance with electromagnetic immunity

Connector insertion/removal
durability

100 times (min.)