Hybrid Terminal Block Hardware Manual

2-6

„Relay Output Specifications Q2 to Q7

„Output delay and contact

‹Relay Output Delay

The output delay is illustrated below.

‹Relay Output Contact

The relay output contact is shown below.

‹Transistor Source Output Contact

The transistor source output contact is shown below.

Number of outputs

6 relay outputs

Output points per common line - COM1 3 NO contacts

Output points per common line - COM2 2 NO contacts

Output points per common line - COM3 1 NO contact

Maximum load current

2 A per output
8 A per common line

Minimum switching load

0.1 mA/DC0.1 V (reference value)

Initial contact resistance

50 m

Ω (max.)

Mechanical life

20,000,000 operations (min.) (rated load 18,000
operations/h)

Dielectric strength

Between output to internal circuit: AC1500 V rms, 1 min
Between output to terminals (COMs): AC750 V rms, 1
min

Connector insertion/removal durability

100 times (min.)

Output delay - turn on time

10 ms (max.) (Bounce time not included)

Output delay - turn off time

5 ms (max.) (Bounce time not included)

ON

OFF

ON

OFF

Command

Output Relay Status

OFF delay: 5 ms (max.)

ON delay: 10 ms (max.)

Qx (Load)

COM

Terminal block

Internal Circuit

N.O

COM (+)

Output

-V

Internal

Circuit