1 indicator leds details, 1 indicator leds details -8, I/o status leds – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 17

Advertising
background image

Hybrid Terminal Block Hardware Manual

1-8

1.4.1

Indicator LEDs Details

„ CANopen Communication LEDs

Standard DRP303-3 defines the RUN and ERR LEDs and their different statuses.

„ I/O status LEDs

LED

Type of flashing

Description

ERR (red)

off

No error.

random flashing

Automatic search for the bus communication speed.

flashing: 1
flash

Warning limit reached. An internal error counter in the
CAN controller has reached or exceeded the error frame
limit threshold number (error frame).

flashing: 2
flashes

Error control event. Detection of a guard event (NMT-
Slave or NMT-master) or a heartbeat event (Heartbeat
consumer)

flashing: 3
flashes

Synchronization error: message not received within the
defined period.

on

Bus OFF. Status of the HTB: Bus OFF.

RUN (green)

random
flashing

Automatic search for the bus communication speed.

continuous
flashing

Module status: Pre-operational.

flashing: 1
flash

Module status: Stopped.

on

Module status: Operational.

Name

LED color

Status

Function

PWR (power)

green

on

Presence of 24 VDC for the HTB

I0 to I11

green

on

Input set to 1

off

Input set to 0

Q0 to Q7

green

on

Active output

off

Inactive output

Advertising