Chapter 3 Installation and Wiring

3-7

3.2.2

CANopen wiring

The CANopen interface uses DSUB 9-pin plug connector. The plug is assigned with the CAN_H, CAN_L and

CAN_GND connections. CAN_H and CAN_L are two physically different bus levels. CAN_GND is the

common reference potential.

„Line termination

To minimize the reflections from the end of the cable, a line termination shall be placed close to the 2 ends of

the bus. Connect both ends of the twisted pair cable(CAN_H and CAN_L) to each LT. Use line termination

whose resistance value is 120

Ω. (5%, 1/4 W maximum)

The cable’s resistance value should be 70m

Ω/m or less.

The above diagrams shows the case used the cable connector “XM2D-0901” by OMRON Co.

GP

Termination
Resistance

Shield

D-sub 9 pin (socket)

CAN-L

Signal

name

2

CAN-H

CAN-GND

FG

Shell