Grounding

Overview

The grounding resistance between the PS-B unit’s Functional Ground (FG) and
Ground must be 100

Ω or less. When using a long grounding wire, check the

resistance and if required replace a thin wire with a thicker wire and place it in a duct.
In addition, please refer to the table below for maximum line lengths for various wire
thicknesses.

Ground Wire Dimensions

Precaution

Dedicated Ground

Connect the Functional Ground (FG) to a dedicated ground.

Shared Ground Allowed

If a dedicated ground is not possible, use a shared ground, as shown.

Wire Thickness

Maximum Line Length

2.5 mm

2

(13 AWG)

30 m (98 ft.)

60 m (196 ft.) round trip.

WARNING

UNINTENDED EQUIPMENT OPERATION

z

Use only the authorized grounding configurations shown below.

z

Confirm that the grounding resistance is 100

Ω or less.

z

Test the quality of your ground connection before applying power to the device.
Excess noise on the ground line can disrupt PS-B unit's operations.

Failure to follow these instructions can result in death, serious injury, or
equipment damage.

Other

Device

Other

Device

PS-B unit