• To improve the noise resistance, be sure to

twist the ends of the power cord wires
before connecting them to the Power con-
nector (Plug).

• The PL unit’s power supply cord should

not be bundled with or kept close to main
circuit lines (high voltage, high current), or
input/output signal lines.

• To reduce noise, make the power cord as

short as possible.

• If the supplied voltage exceeds the PL

unit’s range, connect a voltage transformer.

• Between the line and ground, select a

power supply that is low in noise. If there
is an excess amount of noise, connect an
insulating transformer.

• The temperature rating of field installed

conductors: 75

°C only.

• Use constant voltage and insulating

transformers with capacities exceeding
Power Consumption value.

• Connect a surge absorber to handle

power surges.

• Be sure to ground the surge absorber

(E1) separately from the PL unit (E2).
Select a surge absorber that has a
maximum circuit voltage greater than
that of the peak voltage of the power
supply.

3.

Grounding Cautions

• Be sure to create an exclusive ground for

the Power Cord’s FG terminal. Use a
grounding resistance of 100

Ω, a wire of

2mm

2

or thicker, or your country’s applica-

ble standard.

• The SG (signal ground) and FG (frame

ground) terminals are connected internally
in the PL unit.
When connecting the SG line to another
device, be sure that the design of the sys-
tem/connection does not produce a short-
ing loop.

• The grounding wire should have a cross

sectional area greater than 2mm

2

. Create

the connection point as close to the PL unit
as possible, and make the wire as short as
possible. When using a long grounding
wire, replace the thin wire with a thicker
wire, and place it in a duct.

4.

Input/Output Signal Line Cautions

• All PL Input and Output signal lines must

be separated from all operating circuit
(power) cables.

• If this is not possible, use a shielded cable

and ground the shield.

• To improve noise immunity, it is recom-

mended to attach a ferrite core to the
power cord.

Lightning Surge Absorber

E1

E2

FG

PL

Other
Equipment

Exclusive Grounding

(BEST)

PL unit

Other
Equipment

Common Grounding (OK)

PL unit

Other
Equipment

Common Grounding

(Not OK)

PL unit