Proface APL3000B - Node Box PC User Manual

Page 67

Advertising
background image

PL3000 Series Reference Manual

3-6

‹ LED Indicator

‹ External Input Signals

The PL’s RAS interface connector uses the following input signals.

General-Purpose Input (DIN 2 bits)

This standard digital input is used for error/alert detection in external devices. The input signal uses two bits.

The System Monitor property of the control panel or the API-DLL can be used to enable or disable this

feature, as well as designate what type of processing is to be performed once a signal is received. (Only

the “ON” state of the DIN circuit is detected. The “OFF” state of the DIN circuit cannot be monitored.)

Remote Reset Input

This is the reset signal sent from an external device to the PL. When this signal is enabled, a forced reset

of the PL is performed.

The System Monitor property of the control panel or the API-DLL can be used to enable or disable this

feature.

LED Color

System Status

output condition

Green (Lit)

Normal Operation (Power is ON)

None

Green (Blinking)

System is NOT running (Soft OFF)

None

Orange (Lit)

A RAS error/alert occurred.

LED is enabled via System
Monitor Property.

Orange/Red (Blinking)

Backlight burnout is detected.

None

Not Lit

Power is OFF

-

To enable Remote Reset Input, make sure to check the [Enable] in the Remote reset tab of

System Monitor Property. For Remote reset of System Monitor Property, refer to the following.

Input Voltage

DC12V to 24V

Input Method

Sink / Source Input

Input Current

10mA (DC24V)

Input Resistance

3.6k

Input Points

2 points (common with external reset
input)

Operation Range

ON voltage

DC10V or more

OFF voltage

DC3V or less

Isolation Method

Photocoupler Isolation

Dielectric Strength Voltage

500V or more

SEE

2.2.2 Advanced (page2-7)

3.8.5 Remote reset (page3-35)