<6. Operation>

6-1

IM 01C27H01-01EN

6. Operation

6.1 Preparation for Starting

Operation

This section describes the operation procedure

for the EJX118B as shown in Figure 6.1 when

measuring liquid level in a closed tank, and

EJX438B as shown in Figure 6.2 when measuring

pressure in a tank.

NOTE

It is required to set security and network

information to enable the transmitter to be

connected to the Field Wireless Network. For

more details, refer to section 6.4 “Connecting to

the Field Wireless Network”.

Closed tank

F0601.ai

Transmitter

mounting pipe

50mm (2 inches)

Capillary tube

Diaphragm seal

(high pressure side)

Diaphragm seal

(low pressure side)

Differential pressure

transmitter

Figure6.1

Liquid Level Measurement in a Closed

Tank

F0602.ai

Transmitter

mounting pipe

50mm (2 inches)

Capillary tube

Pressure transmitter

Diaphragm seal

Figure 6.2

Pressure Measurement

(a) Confirm that there is no leak in the connecting

part of each diaphragm seal mounting flange.

(b) Insert batteries into the battery case, and install

to the transmitter. To insert batteries into the

battery case, be careful to polarity of batteries

and battery case. For details of Installation of

battery, refer to section 8.4.4 and 8.4.5.

Battery case is installed in the transmitter when

shipped from the factory, however, batteries are

sold separately and not included.

(c) Using the device configuration tool, confirm

that the transmitter is operating properly. Check

parameter values or change the setpoints as

necessary.

Integral Indicator’s indication can be used to

confirm that the transmitter is operating properly.

For details on how to confirm, refer to subsection

7.4 “Self-Diagnostics”.

ISA100 devices display self-diagnostic information

in an easy-to-understand manner using four

categories (Check function, Maintenance required,

Failure, and Off specification) according to NAMUR

NE107*.

* NAMUR NE107 “Self-Monitoring and Diagnosis of Field

Devices”