<8. Setting Parameters>

8-18

IM 01C27C01-01EN

NOTE

When the device detects AL01 and AL02, the

LCD display stays on regardless of the status

in LCD mode. See Table 9.3 and 9.4 Error

Message Summary for details.

8.3.4 Tag and Device Information

If these are specified when ordering, the designated

Tag No. and device information are set and

shipped. Tag No. and device information can be

checked as follows.

• Procedure to call up the Tag No. and Device

information
- Device Tag ( Software Tag )

This is specified when writing characters (up

to 16 characters) of amplifiers TAG that differ

from characters specified in Tag No.

Refer to section 7.4 “Connection to the Field

Wireless Network” for confirmation.

- Tag Description

This is a universal parameter to store the

comment that describes the content of the

tag located in the TRANSDUCER and AI

blocks.

The AI1, AI2, and AI3 blocks of the AI blocks

correspond to the differential pressure, static

pressure, and temperature, respectively.

• When changing the device information, input

the information based on the following limitation

on the number of characters.
- Message function (up to 32 characters)

TRANSDUCER block:Tag Description

AI1-AI3 block: Tag Description

8.3.5 Unit

The unit parameter is set at the factory before

shipment if specified at the time of order. Follow the

procedure below to change the unit parameter.

• Procedure to call up the Unit Index display

(Units Index)

AI1-AI3 block: Scale.Units Index

To change the Unit display, choose desired

unit among the list of displayed unit selecting

AI1 block as for the differential pressure, AI2

as for the static pressure and AI3 block as for

temperature in the AI blocks.

8.3.6 Range Change

The range values are factory-set as specified by

the customer. To change the range, follow the steps

below.
The measurement span is determined by the upper

and lower range values. In this method, the upper

and lower range values can be set independently,

and the span changes according to the range limit

values sent to the transmitter.

• Procedure to call up the PV Range display

AI1, AI2 block: PV Range

Select the AI1 block for the differential pressure

and the AI2 block for the static pressure, then

select “EU at 0%” and “EU at 100%” displayed

in the PV Range parameters, and input the

lower range and upper range values for the

range, respectively.