<8. Setting Parameters>

8-19

IM 01C27C01-01EN

8.3.7 Output Signal Low Cut Mode Setup

Low cut mode can be used to stabilize the output

signal near the zero point.

( There is 10% of hysteresis at only point of

transition from low to high)
[Setup Low Cut Value]

• Procedure to call up the Lower cutoff* display

AI1 block: Lower cutoff*
Example: setup LOW_CUT of output to 15%
Lower cutoff*

= (“Eu at 100%” - “Eu at 0%”) × 0.15 + “Eu at 0%”

*: “Low Cutoff” is used instead of “Lower cutoff” for

Detachable antenna type (Amplifier housing code: 8 or

9).

[Setup Low Cut Mode]

• Procedure to call up the Low Cut Mode display

AI1 block: Low Cut Mode
Example: Low cut at 20%

F0804.ai

(%)

50

20

0

50 (%)

For low cut in Linear mode

Example:

Low cut 20%

Input

Output

Output

For low cut in Zero mode

(%)

50

20

0

50 (%)

Example:

Low cut 20%

Input

Figure 8.2

Low Cut Mode

The low cut point has hysterisis so that the output

around the point is behaved as below figure.

<Example>

Output mode: Linear

Low cut mode: Zero

Low cut: 20.00%

Output

Setting range:

0 to 20%

Input

0%

(20%)

2%

Low

cut

point

Hystrersis fixed at 10%
of the cut point

F0805.ai

8.3.8 Integral Indicator Setup

The following three displays are available for

the Integral Indicator: differential pressure, static

pressure, and temperature.

The following three variables can be displayed on

the integral indicator: % of differential pressure

range, % of static pressure range, and % of

temperature range.

Available displays

Description

and related parameters

% of range

(PRES %)

Indicates input pressure in –10 to

110% range depending on the set

range (

LRV and URV).

PRES % 45.6 %

% of static pressure

(SP %)

*1

Indicates input static pressure in

–10 to 110% range depending on

the set range (

SP LRV and SP

URV).

SP % 52.6 %

*1:

Available for differential pressure transmitter.

Follow the procedure described in (1) to (2) below

to set the integral indicator.
(1) Display Selection
Display set to Display Selection is displayed on the

integral indicator.

• Procedure to call up the Display Selection

display

TRANSDUCER block: Display Selection

The Display Selection parameter enables the

differential pressure (AI1 block), static pressure

(AI2 block), and temperature (AI3 block) to be

displayed on the LCD. Select whether or not to

enable each block to be displayed.

(2) Cyclic Display
Information in the AI1 to AI3 blocks can be

displayed cyclically according to the display On/Off

setting for the differential pressure (AI1 block), static

pressure (AI2 block), and temperature (AI3 block)

selected in the Display Selection parameter.