<10. Parameter Summary>

10-8

IM 01C27C01-01EN

Object

ID

Attribute

ID

Label

Description

Default

value

Handling

6.

AI2

block

(continued)

53

PV Range

Sets the measurement range.

1. EU at 100% : Indicates input value of the upper

limit.

2. EU at 0% : Indicates input value of the lower limit.

3. Units Index : Indicates the units of the

measurement range.

4. Decimal : Indicates the digit number below the

decimal point.

1. EU at

100% =

25000.000000

EU at 0%

= 0

Units Index

= kPa

Decimal

= 2

W

54

Linearization Type

Select either No Linearization or Square root as a

setting of the output range.

0 = No Linearization :

Provides an output value scaled according to the

PV Range and Scale range settings.

(To use Direct with FF, set the same value for PV

Range and Scale.)

0

W

55

Flow Constant

Indicates the flow coefficient, which shows the

correlation between the flow rate value and square root

value of the pressure.

1.0

W

56

Lower Cutoff

Specifies the low cut value. The unit is subject to

Scale.Units Index.

10

W

57

Cal Cmd

Specifies the calibration method.

0 = CAL_NONE : Initial state in which calibration is

not performed

1 = CAL_LOW : Applies an actual input and adjusts

the lower limit using the value specified in

Calibration Lowest Point.

2 = CAL_HIGH : Applies an actual input and adjusts

the higher limit using the value specified in

Calibration Highest Point.

5 = CAL_CLEAR : Clears the adjustment variable.

0 (reading

value is

always 0)

W

58

Cal Status

Indicates the calibration status.

0 = CAL_NONE : Start-up and default value

1 = CAL_SUCCESS : Indicates that calibration was

successful.

7 = CAL_BAD_TRIM_POINT : Indicates this status

when the adjustment variable is outside of range.

R

59

Calibration Highest

Point

Specifies the higher limit adjustment variable for

adjustment between two points.

---

W

60

Calibration Lowest

Point

Specifies the lower limit adjustment variable for the

adjustment between two points.

---

W

61

Calibration

Minimum Span

Indicates the minimum span of the adjustment

variable.

108 = Gauge pressure

109 = Absolute pressure

---

R

102

Static Process

Type

Selects the gauge pressure or the absolute pressure.

Abs

W

103

SP Select

Parameter to select the High-side pressure or the Low-

side pressure as the static pressure output.

0 = High : Displays the H-side pressure as the static

pressure

1 = Low : Displays the L-side pressure as the static

pressure

High

W

7.

AI3

block

1

Process Value

Al3 is a temperature pressure output object.

Indicates the primary analog value (or corresponding

process value) and status used to execute this

function.

Allows updating data by specifying this for the

Concentrator object.

1. Value: output value of Al object

2. Status: Specify output status of Al object.

1. Value = ---

2. Status = ---

W