Yokogawa EJX210B User Manual

Page 87

Advertising
background image

<10. Parameter Summary>

10-10

IM 01C27C01-01EN

Table 10.2

Diagnostic Status Detail[0]

Bit

Diagnostic Status Detail

Description

Diagnostic Status

assignment bit

NAMUR

DiagnosticDetail_1
31

FC_SENSOR_FAIL

C sensor frequency error

Bit26

F

30

FR_SENSOR_FAIL

R sensor frequency error

Bit26

F

29

CAP_T_SENSOR_FAIL

Capsule temperature sensor failure

Bit26

F

28

CAP_EEPROM_FAIL

Capsule EEPROM failure

Bit26

F

27

CAP_EEP_IRREGULAR

CAP EEPROM version not correct

Bit26

F

26

AMP_T_SENSOR_FAIL

Amplifier temperature sensor failure

Bit27

F

25

AMP_EEPROM_FAIL

Amplifier EEPROM failure

Bit27

F

24

AMP_EEP_IRREGULAR

AMP EEPROM version not correct

Bit27

F

22

G_A_COMM_FAIL

G/A failure

Bit27

F

21

FC_UNOSC_FAIL

C sensor oscillation stop failure

Bit26

F

20

FC_DELTA_T_FAIL

C-side deltaT circuit failure

Bit27

F

19

FR_DELTA_T_FAIL

R-side deltaT circuit failure

Bit27

F

18

WL_AD_FAIL

Battery voltage not detected (AMP failure)

Bit27

F

17

FR_UNOSC_FAIL

R sensor oscillation stop failure

Bit26

F

15

DP_OUTSIDE_LIMIT

Pressure outside of specified range

Bit23

O

14

SP_OUTSIDE_LIMIT

Static pressure outside of specified range

Bit23

O

13

CAPT_OUTSIDE_LIMIT

Capsule temperature outside of specified range

Bit23

O

12

AMPT_OUTSIDE_LIMIT

Amplifier temperature outside of specified range

Bit23

O

7

DP_OUTSIDE_RANGE

Input pressure setting outside of range

Bit22

O

6

SP_OUTSIDE_RANGE

Static pressure setting outside of range

Bit22

O

DiagnosticDetail_2
31

AI1_OUT_OF_SERVICE

AI1 O/S mode

Bit24

C

30

AI2_OUT_OF_SERVICE

AI2 O/S mode

Bit24

C

29

AI3_OUT_OF_SERVICE

AI3 O/S mode

Bit24

C

28

AI1_SIMULATION_ACTIVE

AI1 simulation mode

Bit17

C

27

AI2_SIMULATION_ACTIVE

AI2 simulation mode

Bit17

C

26

AI3_SIMULATION_ACTIVE

AI3 simulation mode

Bit17

C

20

DP_TRIM_SPAN_OUTSIDE

Pressure span adjustment variable outside of range

Bit25

C

19

DP_TRIM_ZERO_OUTSIDE

Pressure zero adjustment variable outside of range

Bit25

C

15

SP_TRIM_SPAN_OUTSIDE

Static pressure span adjustment variable outside of

range

Bit25

C

14

SP_TRIM_ZERO_OUTSIDE

Static pressure zero adjustment variable outside of

range

Bit25

C

13

WL_LOWBAT_ALM

Low battery

Bit19

M

12

CRITICAL_LOWBAT

*1

Detect a decrease in the lowest drive voltage.

Bit20

M

10

WL_DEEPSLP_ALM

Deep sleep due to low battery

Bit20

M

8

LCD_OUTSIDE_LIMIT

LCD display outside of specified range

Bit25

C

*1: Applicable for amplifier housing code 8 or 9.

*2: Applicable for amplifier housing code 7.

F1001.ai

AI algoritm

MODE Target

from operator

from operator

from operator

from transducer

SIMULATE

On

Off

AI

algorithm

Linearization

scaling,

filter

Alert

report

HiHi etc

PV

Auto

O/S

Man

Publish

Value

& Status

PV

PV

Value

& Status

Value

& Status

Value

& Status

Mode and

PV.Status handling

SWITCH

SIMULATE

_VALUE

Figure 10.1 Example schema of analog input object