2 zero-gain adjustment, 3 starting operation, 4 connecting to the field wireless network – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 30: Zero-gain adjustment -2, Starting operation -2, Connecting to the field wireless network -2, 2 zero-gain adjustment important, Important

Advertising
background image

<6. Operation>

6-2

IM 01C50E01-01EN

6.2 Zero-gain Adjustment

IMPORTANT

After performing zero-gain adjustment, do not

power off the transmitter immediately. Turning off

the power within 30 seconds resets the zero-

gain adjustment value to the value before the

adjustment.

Furthermore, setting the sensor type

automatically resets the zero-gain adjustment

value to the factory setting

When the preparation for starting operation is

completed, perform a zero-gain adjustment as

necessary.

This transmitter is fully calibrated at the factory and

basically re-cablibration is not necessary; however,

users can make the zero-gain adjustment.

The zero-gain adjustment of this transmitter can be

performed by the following steps.

1) Apply the lower limit of process temperature

to the sensor. Set the lower limit temperature

using the device configuration tool.

2) Apply the upper limit of process temperature

to the sensor. Set the upper limit temperature

using the device configuration tool.

The zero-gain adjustment should be performed

when the input to the temperature sensor is

stabilized.

For details on the zero-gain adjustment, refer to

subsection 7.3.13 Input calibration.

6.3 Starting Operation

Ensure that the installation, the wiring, the network

connection, and the action of the transmitter are

correct before starting operation.

IMPORTANT

Close the terminal box cover and the amplifier

cover. Screw each cover in tightly until it will not

turn further.

6.4 Connecting to the Field

Wireless Network

Preparation work prior to connecting to a

field wireless network

This transmitter does not need to be connected

with a physical wire. Instead of physical wiring, it

is necessary to set the field wireless devices to

communicate with before installing the transmitter.

This procedure is called a provisioning.

This transmitter supports provisioning via infrared

communication using a provisioning device and

can be securely connected to a network. If the

provisioning information is not set, the transmitter

cannot be connected to the field wireless network.
Provisioning:

Provisioning is work to set the security and

network information to enable the transmitter

to be connected to the field wireless network.

This transmitter supports a provisioning method

using infrared communication.

For details on provisioning using a provisioning

device, connecting to a field wireless network and

the setting procedure, refer to the User’s Manual,

FieldMate Versatile Device Management Wizard

(IM 01R01A01-01E), YFGW710 Field Wireless

Integrated Gateway (IM 01W01F01-01EN), and

YFGW410 Field Wireless Management Station (IM

01W02D01-01EN).

F0602.ai

Within 30cm

Figure 6.2

Provisioning Example

Advertising