<7. Setting Parameters>

7-14

IM 01C50E01-01EN

1) Setting the Sensor Type

■ Procedure to call up the sensor type setting

parameter (Lin Type)

AI1/AI2 block: Lin Type
Set the sensor type.
■ Procedure to call up the sensor type information

parameter (Sensor Range)

AI1/AI2 block: Sensor Range : EU at 0%

AI1/AI2 block: Sensor Range : EU at 100%
Displays the lower and upper limit values that

can be measured by the sensor type set in the

sensor type setting parameter (Lin Type) as the

lower limit information parameter (EU at 0%)

and the upper limit information parameter (EU

at 100%).

2) Setting the Temperature Sensor

Connection

This is set when using the resistance temperature

sensor.

■ Procedure to call up the connection setting

parameter (Sensor Connection)

AI1 block: Sensor Connection
Select and set any of the 2-, 3-, or 4-wire

methods corresponding to the resistance

temperature sensor.

AI2 block: Sensor Connection
Select and set either 2- or 3-wire methods

corresponding to the resistance temperature

sensor.

NOTE

In 4-wire connection for the dual sensor input

type, first set "Not Used" to AI2: Lin Type, then

set the AI1: Lin Type/Sensor Connection.

3) Setting the Cold Junction Compensation

(CJC) of the Thermocouple Sensor

This is set when using the thermocouple sensor.

■ Procedure to call up CJC function

parameter(Selection of Reference Junction)

AI1/AI2 block: Selection of Reference Junction
Select the CJC function.

To calibrate voltage for the thermocouple

input, set the cold junction temperature to No

Reference (0).

■ Procedure to call up external temperature

Compensation parameter(External Reference

Junction Value)

AI1/AI2 block: External Reference Junction

Value

In the CJC function parameter (Selection

of Reference Junction), the cold junction

temperature value of the thermocouple is

selected the external (2), set the external

compensation temperature.

The CJC is also called reference junction

compensation.

IMPORTANT

Setting the sensor type automatically resets the

zero-gain adjustment value to the factory setting.

7.3.10 Assignment to AI Object

Output of the process value via field wireless

network is set by AI1/AI2 block.

Either actual target value or % value of the

temperature, the voltage, and resistance is set as

the output of process value from the AI1/AI2 block.

7.3.11 Burnout Setting

This function is applicable for dual input type with a

detachable antenna, Amplifier housing code 8 and

9. Specify the direction of PV value at the burnout.

• AI1/AI2 block: Burn Out Type
Enable Hard Switch: the direction specified by

hardware switch

Up: Higher side

Down: Lower side

Selecting Up and Down disables the setting of

hardware switch

7.3.12 Write Protect

Hardware write protection and software write

protection functions are available for this

transmitter.

1) Procedure to call up the protection setting

parameter (UAP Option)

The following settings can be configured in the

UAP Option parameter.

- Setting to enable or disable software write

protection.